2004-08-05 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS FOR THE WAREHOUSE AS WELL
 AS THE OFFICE & SHOW ROOM AREAS IN
 ACCORDANCE WITH THE 2001 FBC(M) 403.3.
  
 2.PLEASE INDICATE IF ANY CHEMICALS
 WILL BE STORED IN THE WAREHOUSE AREA.
  
 3.THE CONDENSING UNIT STANDS SHALL
 COMPLY WITH THE 2001 FBC 1511.7 FOR THE
 HEIGHT REQUIREMENT FROM THE ROOF SURFACE
 TO THE BOTTOM OF THE SUPPORT RAIL.
  