2004-07-29 00:00:001) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" NUMBERS ARE REQUIRED.
  
 2) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 4) ILLUMINATED EXIT SIGN IN SHOWROOM # 2
 IS NOT NEEDED THAT LEADS PERSONS INTO
 THE WAREHOUSE AREA.
  
 5) A KNOX-BOX WILL BE REQUIRED.
  
 6) REQUIRED FIRE ALARM SYSTEM PANEL
 USED FOR MONITORING MUST BE UL LISTED
 FOR CENTRAL STATION SERVICE.
  
 7) LOCKABLE KNOX-BOX CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 8) A FIRE HYDRANT SHALL BE LOCATED
 WITHIN 150 FEET OF THE FIRE DEPARTMENT
 CONNECTION. THE EXISTING FIRE HYDRANT
 SHOWN MAY NOT MEET THIS REQUIREMENT.
 PLEASE ADVISE.
  
 9) SPARE SPRINKLER HEAD BOX WILL
 BE REQUIRED.
  
 10) ALL CONSTRUCTION, RENOVATION AND
 DEMOLITION SHALL CONFORM TO NFPA 241.
  
 11) TAMPER SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 12) PLEASE INDICATE WHAT WILL BE STORED
 ON THE RACKS. WHAT TYPE OF PACKAGING
 WILL THESE ITEMS BE STORED IN.
  
 13) PLEASE CLEARLY ILLUSTRATE ALL
 PORTABLE FIRE EXTINGUISHER LOCATIONS.
 (OFFICE)
 14) PLEASE CLEARLY ILLUSTRATE ALL
 EMERGENCY LIGHT FIXTURE LOCATIONS.
  
 15) EXIT SIGNS WILL BE BLOCKED IN
 WAREHOUSE AREA BY RACKS. ADDITIONAL
 EXIT SIGNS APPEAR TO BE NEEDED TO DIRECT
 PERSONS TO THE EXITS. EXIT LOCATIONS
 SHALL BE OBVIOUS AND DIRECT.
  
 16) WHY ARE THERE NO HOSE VALVES IN
 WAREHOUSE AREA.
  
 17) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL