Plan Review Notes For Permit 04070529 |
Permit Number |
04070529 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-10-18 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | PIPE SIZING FOR EXISTING AND NEW PIPE | | ARE NOT SUFFICIENT FOR THE ADDED LOAD OF | | THE POOL HEATER @ 100'. EIGHER A 2 LB | | SYSTEM WITH A REGULATOR OR LARGER PIPE | | IS REQUIRED. TABLE 402(2). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|