2004-08-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE CONDUIT & WIRE SIZE
 FOR THE FEEDER BETWEEN THE DISCONNECT
 AND PANEL ON THE RISER DIAGRAM. ALSO
 SEE 250.122 FOR GROUNDING CONDUCTOR.
  
 2} PLEASE SEE THAT THE REQUIRED BATH
 CIRCUIT 210.11(C)(3) IS LABELED "GAS
 BBQ" ON THE SCHEDULE.
  
 3} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 4} THE REQUIRED SMOKE DETECTORS PER
 NFPA-72 8-1.4.1.6.2 MUST BE SHOWN ON
 THE PLAN.
  
 5} THE TITLE BLOCK INDICATES A
 CORPORATION, THE AA NUMBER MUST BE IN
 THE TITLE BLOCK. SEE 61G1-16.004 FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW