Plan Review Notes For Permit 04070525 |
Permit Number |
04070525 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-08-09 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE INDICATE CONDUIT & WIRE SIZE | | FOR THE FEEDER BETWEEN THE DISCONNECT | | AND PANEL ON THE RISER DIAGRAM. ALSO | | SEE 250.122 FOR GROUNDING CONDUCTOR. | | | | 2} PLEASE SEE THAT THE REQUIRED BATH | | CIRCUIT 210.11(C)(3) IS LABELED "GAS | | BBQ" ON THE SCHEDULE. | | | | 3} PLEASE LIST THE REQUIRED ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 4} THE REQUIRED SMOKE DETECTORS PER | | NFPA-72 8-1.4.1.6.2 MUST BE SHOWN ON | | THE PLAN. | | | | 5} THE TITLE BLOCK INDICATES A | | CORPORATION, THE AA NUMBER MUST BE IN | | THE TITLE BLOCK. SEE 61G1-16.004 FAC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|