Date |
Text |
2004-07-19 00:00:00 | ************* UNSAT **************** |
| |
| 1)NOTE: PLEASE SUBMIT TWO COPIES OF |
| ALL PLANS SUBMITTED.104.1 |
| ALSO MAY NOT BE DONE IN PENCIL. |
| |
| 2)NOTE: PLEASE SEE MISSING LAUNDRY CIR |
| REQUIRED 220.16 |
| |
| 3)NOTE: PLEASE PROVIDE PANEL SCHEDULES |
| WITH ALL MIN CIRCUITS REQUIRED UNDER |
| NEC 210.52,210.11. 220 |
| PLEASE INCLUDE OCP FOR SUB-PANEL AS |
| SHOWN. |
| |
| 4 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 7)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| |
| 8)NOTE: : PLEASE VERIFY PLANS SHOW |
| WASHER, DRYER AND WATER HEATER OUTSIDE? |
| PLEASE SEE FBC FOR INSTALLATION OF |
| WH'S OUTSIDE. WASHER, DRYER MAY NOT BE |
| PLACED OUTSIDE UNLESS CLOSED IN WEATHER |
| PROOF ENCLOSURE. |
| |
| 9)NOTE: PLEASE SEE FBC 104.2.1, PLANS |
| MUST HAVE PRINTED NAME AND SIGNATURE OF |
| PERSON RESPONSIBLE FOR PLANS. |
| |
| 10)NOTE: PLANS NEED TO CONTAIN RM |
| DESIGNATIONS. PLEASE ALSO INDICATE DOORS |
| DOORWAYS IN TO RMS. |
| |
| 11)NOTE: PLEASE SEE PANEL LOCATION(S) |
| REQ'D TO MEET 110.26, 408.7 ETC. |
| |
| 12)NOTE: PLEASE INCLUDE RATINGS OF PANEL |
| -S SHOWN ON RISER. |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| 13)NOTE: PLEASE SEE FBC 104.6.5, PLEASE |
| ADJUST VALUE FOR SCOPE OF WORK. |
| VALUE IS TO INCLUDE ALL LABOR AND MATER- |
| -IALS EVEN IF OWNER SUPPLIED. |
| VALUE MAY BE ADJUSTED BY REFERENCE TO |
| MARSHALLS & SWIFT PRICING GUIDE. |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |