Plan Review Notes
Plan Review Notes For Permit 04070432
Permit Number 04070432
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} CIRCUIT # 21B IS SHOWN AT 15 AMPS
 SERVING THE DINING ROOM AND THE FOYER.
 PLEASE NOTE THAT THE DINING ROOM
 RECEPTACLES MUST COMPLY WITH
 210.52(B)(1) & (2), 20 AMP, WITH NO
 OTHER OUTLETS.
  
 2} CIRCUITS B2 & B4 IN THE KITCHEN MUST
 ALSO COMPLY WITH 210.52(B). CIRCUIT B4
 ALSO APPEARS IN THE MASTER BED ROOM IN
 VIOLATION.
  
 3} THE RECEPTACLES SERVING KITCHEN
 COUNTERTOPS MUST BE GFI PER 210.8(A)(6).
  
 4} THE ISLAND MUST HAVE A RECEPTACLE PER
 210.52(C)(2), GFI PER 210.8(A)(6).
  
 5} THE SMOKE DETECTOR AT THE GUEST BATH
 MUST BE 3' FROM THAT DOOR PER 8-1.4.2
 NFPA-72.
  
 6} THE MASTER BATH MUST COMPLY WITH 240.
 52(C)(3), CLOSET OUTLETS ARE IN
 VIOLATION.
  
 7} ALL BATH RECEPTACLES MUST BE GFI PER
 210.8(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW