Plan Review Notes For Permit 04070432 |
Permit Number |
04070432 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-16 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} CIRCUIT # 21B IS SHOWN AT 15 AMPS | | SERVING THE DINING ROOM AND THE FOYER. | | PLEASE NOTE THAT THE DINING ROOM | | RECEPTACLES MUST COMPLY WITH | | 210.52(B)(1) & (2), 20 AMP, WITH NO | | OTHER OUTLETS. | | | | 2} CIRCUITS B2 & B4 IN THE KITCHEN MUST | | ALSO COMPLY WITH 210.52(B). CIRCUIT B4 | | ALSO APPEARS IN THE MASTER BED ROOM IN | | VIOLATION. | | | | 3} THE RECEPTACLES SERVING KITCHEN | | COUNTERTOPS MUST BE GFI PER 210.8(A)(6). | | | | 4} THE ISLAND MUST HAVE A RECEPTACLE PER | | 210.52(C)(2), GFI PER 210.8(A)(6). | | | | 5} THE SMOKE DETECTOR AT THE GUEST BATH | | MUST BE 3' FROM THAT DOOR PER 8-1.4.2 | | NFPA-72. | | | | 6} THE MASTER BATH MUST COMPLY WITH 240. | | 52(C)(3), CLOSET OUTLETS ARE IN | | VIOLATION. | | | | 7} ALL BATH RECEPTACLES MUST BE GFI PER | | 210.8(A)(1). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|