Plan Review Notes For Permit 04070258 |
Permit Number |
04070258 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-16 00:00:00 | **********DENIED************************ | | 1) ON SHEETS FP-2 AND FP-3 APPEARS THAT | | THE PUMP ROOM, GENERATOR ROOM, ELECTRIC | | ROOM, AND TRANSFORMER VAULT ARE NOT FIRE | | SPRINKLER PROTECTED. | | | | 2) PLEASE BE ADVISED THAT THE FOUR | | STANDPIPES REQUIRES 1250 GPM FIRE PUMP | | AND SEPARATE PERMIT APPLICATION AND CUT | | SHEETS MAYBE REQUIRED. | | | | NATE MCCRAY, CAPTAIN | | 835-2910 OR 805-6722 |
|