2004-08-16 00:00:00**********DENIED************************
 1) ON SHEETS FP-2 AND FP-3 APPEARS THAT
 THE PUMP ROOM, GENERATOR ROOM, ELECTRIC
 ROOM, AND TRANSFORMER VAULT ARE NOT FIRE
 SPRINKLER PROTECTED.
  
 2) PLEASE BE ADVISED THAT THE FOUR
 STANDPIPES REQUIRES 1250 GPM FIRE PUMP
 AND SEPARATE PERMIT APPLICATION AND CUT
 SHEETS MAYBE REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722