Plan Review Notes For Permit 04070185 |
Permit Number |
04070185 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-15 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE SERVICE CALCULATED LOAD IS 240 | | AMPS. THE RISER INDICATES A 200 AMP | | MAIN. THE SERVICE ENTRANCE CONDUCTORS | | MUST BE 4/0 PER 310.15(B)(6). | | | | 2} THE SERVICE MUST BE 250 AMPS PER | | 230.42. | | | | | | 3} THE GEC MUST BE #2 CU PER 250.66. | | | | 4} THERE MUST BE OUTSIDE RECEPTACLES | | FRONT AND REAR PER 210.52(E). | | | | 5} THE GARAGE RECEPTACLES NUST BE GFI | | PER 210.8(A)(2). | | | | 6} THERE ARE NUMEROUS LOCATIONS THAT DO | | NOT COMPLY WITH RECEPTACLE SPACING | | REQUIREMENT PER 210.52 ALL. SEE REVIEWED | | SET FOR SOME LOCATIONS. | | | | 7} THE KITCHEN AND DINING ROOM | | RECEPTACLES ARE NOT SHOWN ON SHEET 3 OF | | 3. SEE 210.52, 210.11 (C)(1), 210.52(B) | | AND 210.8(A)(6). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|