Plan Review Notes
Plan Review Notes For Permit 04070185
Permit Number 04070185
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-15 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SERVICE CALCULATED LOAD IS 240
 AMPS. THE RISER INDICATES A 200 AMP
 MAIN. THE SERVICE ENTRANCE CONDUCTORS
 MUST BE 4/0 PER 310.15(B)(6).
  
 2} THE SERVICE MUST BE 250 AMPS PER
 230.42.
  
  
 3} THE GEC MUST BE #2 CU PER 250.66.
  
 4} THERE MUST BE OUTSIDE RECEPTACLES
 FRONT AND REAR PER 210.52(E).
  
 5} THE GARAGE RECEPTACLES NUST BE GFI
 PER 210.8(A)(2).
  
 6} THERE ARE NUMEROUS LOCATIONS THAT DO
 NOT COMPLY WITH RECEPTACLE SPACING
 REQUIREMENT PER 210.52 ALL. SEE REVIEWED
 SET FOR SOME LOCATIONS.
  
 7} THE KITCHEN AND DINING ROOM
 RECEPTACLES ARE NOT SHOWN ON SHEET 3 OF
 3. SEE 210.52, 210.11 (C)(1), 210.52(B)
 AND 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026