Date |
Text |
2004-08-25 00:00:00 | *************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 3) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| PLEASE SEE SOME MISSING. |
| |
| 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| SHOWING MIN CIRCUITING REQ'D UNDER NEC |
| 2002. |
| |
| 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN TO DETACH- |
| -ED PANEL AT GARAGE. |
| |
| 8)NOTE: PLEASE SEE MAIN HOUSE HAS A NOTE |
| FOR PANEL AT GROUND FLR YET THERE IS A |
| PANEL ALSO SHOWN ON SECOND FLR?? |
| |
| 9 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 10)NOTE:PLEASE SEE MISSING RECEPT REQ'D |
| FOR A/C EQUIPMENT. 210.63 |
| |
| 11)NOTE: PLEASE SHOWS REQ'D DISC'S FOR |
| A/C EQUIPMENT. PER 440.11 |
| PLEAS ALSO SHOWN A/C UNIT LOCATIONS. |
| |
| 12)NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210.70 AND LS-101 5-8 |
| **DETACHED EGRESS TO OUTSIDE** |
| |
| 13)NOTE: PLEASE SEE MISSING RECEPTS TO |
| BE W/IN 3' OF SINKS. 210.52D |
| |
| 14)NOTE: PLEASE SEE EXISTING GARAGE |
| AREA WILL REQUIRE LT/ GFI. 210.70, |
| 210.52G, 210.8 |
| |
| 15)NOTE: PLEASE ALSO SEE DEATCHED BLDG |
| RMS WILL ALSO REQUIRE ARC FAULT. |
| PLEASE SEE RM W/ ONLY ONE RECEPT SHOWN. |
| /NOT SHOWN AS A CLOSET?? 210.52 |
| |
| 16)NOTE: PLEASE SHOW ROOM DESIGNATION |
| ON PLANS. |
| |
| 17)NOTE: *** PLANS CAME IN AS A REVISION |
| UNDER BLDG/DEMO/INT REMOD PERMIT. |
| PLEASE SUBMIT PLANS UNDER AN ELECTRICAL |
| PERMIT APPLICATION WITH VALUE AND |
| COMPLETE SCOPE OF ELECTRICAL WORK. |
| PLANS SHOW ALL ELECTRICAL BEING BROUGHT |
| UP TO CODE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |