Plan Review Notes
Plan Review Notes For Permit 04070047
Permit Number 04070047
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE SOME MISSING.
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 SHOWING MIN CIRCUITING REQ'D UNDER NEC
 2002.
  
 7)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO DETACH-
 -ED PANEL AT GARAGE.
  
 8)NOTE: PLEASE SEE MAIN HOUSE HAS A NOTE
 FOR PANEL AT GROUND FLR YET THERE IS A
 PANEL ALSO SHOWN ON SECOND FLR??
  
 9 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 10)NOTE:PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 11)NOTE: PLEASE SHOWS REQ'D DISC'S FOR
 A/C EQUIPMENT. PER 440.11
 PLEAS ALSO SHOWN A/C UNIT LOCATIONS.
  
 12)NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
 **DETACHED EGRESS TO OUTSIDE**
  
 13)NOTE: PLEASE SEE MISSING RECEPTS TO
 BE W/IN 3' OF SINKS. 210.52D
  
 14)NOTE: PLEASE SEE EXISTING GARAGE
 AREA WILL REQUIRE LT/ GFI. 210.70,
 210.52G, 210.8
  
 15)NOTE: PLEASE ALSO SEE DEATCHED BLDG
 RMS WILL ALSO REQUIRE ARC FAULT.
 PLEASE SEE RM W/ ONLY ONE RECEPT SHOWN.
 /NOT SHOWN AS A CLOSET?? 210.52
  
 16)NOTE: PLEASE SHOW ROOM DESIGNATION
 ON PLANS.
  
 17)NOTE: *** PLANS CAME IN AS A REVISION
 UNDER BLDG/DEMO/INT REMOD PERMIT.
 PLEASE SUBMIT PLANS UNDER AN ELECTRICAL
 PERMIT APPLICATION WITH VALUE AND
 COMPLETE SCOPE OF ELECTRICAL WORK.
 PLANS SHOW ALL ELECTRICAL BEING BROUGHT
 UP TO CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]