Plan Review Notes
Plan Review Notes For Permit 04061388
Permit Number 04061388
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-02 00:00:00************* UNSAT *************
  
 1)NOTE: PLANS DO NOT INDICATE EXISTING
 SERVICE AND/OR LOCATION FOR GROUPING OF
 MAINS. 230.72
 ADDTIONAL SERVICE AS SHOWN IS NOT PERMIT
 -TED. 230.2
  
 2)NOTE: PLEASE SEE 250.6,250.24, EQUIP-
 -MENT GROUNDING IS ONLY INSTALLED AFTER
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE SEE PLANS ARE SEALED
 COPIES. PLANS ARE REQUIRED TO HAVE AN
 ORIGINAL SIGNATURE PER FS 471.025
 PLEASE ALSO SEE FS REQUIRE A SIGNATURE
 AS SHOWN ON LICENSE/SEAL. INITIALS
 ARE NOT ACCEPTABLE.
 PLEASE SEE ONE SET OF PLANS ARE BEING
 RETAINED FOR FILE FOR ABOVE REFERENCE.
 FAC 61G15-23.002
 PLEASE SEE BOTH SETS ARE COPIES OF SIG-
 -NATURE WITH RAISED SEAL. ONLY ONE SET
 IS BEING RETURNED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  