2005-11-08 00:00:00 | ************* UNSAT ************* |
| |
| 1)NOTE: PLEASE CORRELATE RISER, PANEL |
| SCHEDULES AND LOAD CALCULATIONS. |
| |
| PLEASE SEE RISER SHOW PANEL "E" AS 60A |
| MCB, 30CIR AND PANEL SHOWS AS 60A MLO, |
| 12 CIR. |
| PLEASE SEE RISER SHOWS "E" BEING FED |
| FROM PANEL "B", HOWEVER PANEL "A" SHOWS |
| FEED FOR PANEL "E". |
| PLEASE ALSO SEE PANEL "D" ON RISER FROM |
| PANEL "B", YET PANEL "A" IS SHOWN |
| FEEDING THIS PANEL. |
| PLEASE SEE PLANS INDICATE "E" ON MAIN |
| HOUSE, AND ALSO SHOWS A DISCONNECT AT |
| THIS LOCATION. |
| IF INDEED PANEL "E" IS MLO, THEN A |
| DISCONNECT WILL BE REQUIRED. 225.31. |
| PLEASE NOTE THIS PANEL "E" ON PLANS FOR |
| GAZEBO UNDER SEPARATE PERMIT. |
| |
| PLEASE RE-FIGURE LOAD CALCULATIONS FOR |
| PANEL "C". PLEASE SEE LOAD IS SHOWN AT |
| 150 A'S, HOWEVER THIS PANEL SHOWS 100A |
| FEED ON PANEL "B". |
| PLEASE VERIFY LOADS AND ADJUST AWG ETC |
| AS NESS. |
| |
| 2)NOTE:PLEASE SEE MIN CLEARENCE FOR |
| PANEL "D" |
| IS STILL NOT INDICATED. PLEASE ALSO SEE |
| DISC FOR A/C UNIT. |
| 110.26 |
| |
| |
| 3)NOTE: PLEASE SEE SPECS FOR NEW ATS |
| SWITCHES HAVE BEEN SUBMITTED, HOWEVER |
| PLEASE INDICATE WHICH UNIT WAS USED, |
| 3-POLE, 4-POLE ETC. |
| PLEASE ALSO VERIFY WHERE A LISTING FROM |
| A NRTL IS SHOWN ON SPECS. |
| SERVICE EQUIPMENT? ETC. |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |