Date |
Text |
2005-10-08 00:00:00 | ********* UNSAT *********** |
| |
| |
| 1)NOTE: PLEASE SEE PLANS ARE NOW COMING |
| IN WITH ALL NEW LOW VOLTAGE SYSTEMS |
| WHICH HAVE NOT BEEN PERMITTED. |
| PLEASE SUBMIT COMPLETE PLANS AND PERMIT |
| APPLICATION FOR ALL LV SYSTEMS WITH THE |
| EXCEPTION OF TELEPHONE, CATV AND ALARM. |
| PLEASE SEE HOME AUDOMATION SYSTEM MAY BE |
| REVISED AND INLCUDED WITH MAIN |
| ELECTRICAL CONTRACTOR AS LONG AS THE |
| CONTRACTOR IS TAKING FULL RESPONSIBILTY |
| FOR SUCH WORK. PLEASE ALSO KNOW, IF |
| EXISTING ELECTRICAL CONTRACTOR IS TAKING |
| THE RESPONSIBILITY, REVISED PLANS WOULD |
| ALSO INLCLUDE A VALUATION ADJUSTMENT TO |
| INCLUDE ALL NEW SYSTEMS. LABOR AND |
| MATERIALS. |
| PLEASE PROVIDE SIGNED CONTRACTS FOR |
| SCOPE OF WORK.104.6.5 FBC CITY WIDE |
| ADMINISTRATIVE CODE. |
| ALL LV IS NOT INCLUDED IN ELECTRICAL |
| CONTRACTORS PERMIT. |
| |
| 2)NOTE: PLEASE SEE RISER DIAGRAM HAS |
| BEEN COMPLETELY REVISED TO INCLUDED ATS |
| SWITCHES, NEW PANELS ETC. |
| PLEASE SEE THIS WILL ALSO BE REQUIRED TO |
| UPDATE VALUE. |
| |
| 3)NOTE:PLEASE SEE NEW PANEL "E" WHICH |
| INDICATES A NEW GAZEBO, HOWEVER THIS |
| "GAZEBO" IS NOT ON PLANS. |
| PLEASE SEE THAT BLDG MAY REQUIRE GAZEBO |
| TO BE UNDER A SEPARATE PERMIT. IF NOT, |
| PLEASE SUBMIT REVISE BLDG PLANS, SURVEY |
| FOR ZONING ETC. |
| IF GAZEBO IS A DETACHED BLDG, PLEASE SEE |
| THAT PANEL "E" WILL BE REQUIRD TO HAVE A |
| MCB. 225.31 |
| PLEASE ALSO SEE LOACTION WILL HAVE TO BE |
| DETERMINED FOR CODE COMPLIANCE ONCE |
| PLANS ARE SUBMITTED. |
| PLEASE INCLUDE NEW GROUNDING ELECTRODE |
| SYSTEM AT DETACHED BLDG.250.32 |
| FOOTER STEEL, CWP ETC. |
| 250.50 |
| |
| 4)NOTE: PLEASE SUBMIT MORE INFORMATION |
| FOR HOME AUTOMATION PANELS. PANEL"C" |
| INDICATES 60A,50 ETC OCP FEEDING ????? |
| 240.4,310.16, 215.5 |
| |
| 5)NOTE: PLEASE SUBMIT COMPLETE |
| MANUFACTURE SPECS FOR ATS'S. |
| NOT INCLUDED UNDER THIS PERMIT. |
| |
| 6)NOTE: PLEASE SEE 210.52 WHICH REQUIRES |
| RECEPT SPCING TO MEET CODE ALONG RAIL |
| ARE IN BILLIARD /LOUNGE. RAILIS |
| CONSIDERED WALL SPACE. |
| |
| 7)NOTE: PLEASE VERIFY TAPPED CONDUCTORS |
| IN GUTTER TO ATS'S SW CAN NOT BE |
| VERIFIED AS APPLICATION FOR GENERATOR |
| HAS BEEN SUBMITTED. |
| |
| 8)NOTE: PLEASE SEE 110.26 FOR MIN |
| CLEARNECE REQUIRED FOR POOL PANEL. |
| |
| PLEASE SUBMIT ALL PERMIT APPLICATIONS |
| FOR SCOPE OF REQUIRED TO BE UNDER |
| SEPARATE PERMITS. |
| PLEASE CORRECT PLANS FOR ABOVE COMMENTS. |
| PLEASE SUBMIT ADJUST VALUES. |
| PLEASE RE-SUBMIT THESE PLANS AFTER THIS |
| IS DONE. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |
2005-10-07 00:00:00 | IN ELEC FOR REVIEW. |