Plan Review Notes
Plan Review Notes For Permit 04061352
Permit Number 04061352
Review Stop E
Sequence Number 4
Notes
Date Text
2005-10-08 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH ALL NEW LOW VOLTAGE SYSTEMS
 WHICH HAVE NOT BEEN PERMITTED.
 PLEASE SUBMIT COMPLETE PLANS AND PERMIT
 APPLICATION FOR ALL LV SYSTEMS WITH THE
 EXCEPTION OF TELEPHONE, CATV AND ALARM.
 PLEASE SEE HOME AUDOMATION SYSTEM MAY BE
 REVISED AND INLCUDED WITH MAIN
 ELECTRICAL CONTRACTOR AS LONG AS THE
 CONTRACTOR IS TAKING FULL RESPONSIBILTY
 FOR SUCH WORK. PLEASE ALSO KNOW, IF
 EXISTING ELECTRICAL CONTRACTOR IS TAKING
 THE RESPONSIBILITY, REVISED PLANS WOULD
 ALSO INLCLUDE A VALUATION ADJUSTMENT TO
 INCLUDE ALL NEW SYSTEMS. LABOR AND
 MATERIALS.
 PLEASE PROVIDE SIGNED CONTRACTS FOR
 SCOPE OF WORK.104.6.5 FBC CITY WIDE
 ADMINISTRATIVE CODE.
 ALL LV IS NOT INCLUDED IN ELECTRICAL
 CONTRACTORS PERMIT.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM HAS
 BEEN COMPLETELY REVISED TO INCLUDED ATS
 SWITCHES, NEW PANELS ETC.
 PLEASE SEE THIS WILL ALSO BE REQUIRED TO
 UPDATE VALUE.
  
 3)NOTE:PLEASE SEE NEW PANEL "E" WHICH
 INDICATES A NEW GAZEBO, HOWEVER THIS
 "GAZEBO" IS NOT ON PLANS.
 PLEASE SEE THAT BLDG MAY REQUIRE GAZEBO
 TO BE UNDER A SEPARATE PERMIT. IF NOT,
 PLEASE SUBMIT REVISE BLDG PLANS, SURVEY
 FOR ZONING ETC.
 IF GAZEBO IS A DETACHED BLDG, PLEASE SEE
 THAT PANEL "E" WILL BE REQUIRD TO HAVE A
 MCB. 225.31
 PLEASE ALSO SEE LOACTION WILL HAVE TO BE
 DETERMINED FOR CODE COMPLIANCE ONCE
 PLANS ARE SUBMITTED.
 PLEASE INCLUDE NEW GROUNDING ELECTRODE
 SYSTEM AT DETACHED BLDG.250.32
 FOOTER STEEL, CWP ETC.
 250.50
  
 4)NOTE: PLEASE SUBMIT MORE INFORMATION
 FOR HOME AUTOMATION PANELS. PANEL"C"
 INDICATES 60A,50 ETC OCP FEEDING ?????
 240.4,310.16, 215.5
  
 5)NOTE: PLEASE SUBMIT COMPLETE
 MANUFACTURE SPECS FOR ATS'S.
 NOT INCLUDED UNDER THIS PERMIT.
  
 6)NOTE: PLEASE SEE 210.52 WHICH REQUIRES
 RECEPT SPCING TO MEET CODE ALONG RAIL
 ARE IN BILLIARD /LOUNGE. RAILIS
 CONSIDERED WALL SPACE.
  
 7)NOTE: PLEASE VERIFY TAPPED CONDUCTORS
 IN GUTTER TO ATS'S SW CAN NOT BE
 VERIFIED AS APPLICATION FOR GENERATOR
 HAS BEEN SUBMITTED.
  
 8)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARNECE REQUIRED FOR POOL PANEL.
  
 PLEASE SUBMIT ALL PERMIT APPLICATIONS
 FOR SCOPE OF REQUIRED TO BE UNDER
 SEPARATE PERMITS.
 PLEASE CORRECT PLANS FOR ABOVE COMMENTS.
 PLEASE SUBMIT ADJUST VALUES.
 PLEASE RE-SUBMIT THESE PLANS AFTER THIS
 IS DONE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
2005-10-07 00:00:00IN ELEC FOR REVIEW.