Date |
Text |
2004-07-20 00:00:00 | *************** UNSAT ************* |
| |
| PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| REVIEWS WERE NOT ADDRESSED COMPLETELY. |
| |
| 1 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| PLANS INDICATE EST 118 RECESSED LTS, YET |
| PANELS INDICATE 50 EACH PANEL? |
| PLEASE ALSO SEE EACH PANEL SHOWS ALL |
| 50 LTS ON ONE CIRCUIT. THESE CIRCUITS |
| ARE 15A #14. THESE LOADS MAY NOT BE ON |
| ONLY TWO CIRCUITS. |
| |
| 2)NOTE: PLEASE SEE LOAD CALCS FOR PANEL |
| "C" WERE NOT CHANGED. PLEASE SEE ALL |
| CONTINUOUS LOADS MUST BE FIGURED AT 125% |
| 220.14,430.24,25,26. |
| |
| 3)NOTE: PLEASE SEE AHU #4 OCP HAS BEEN |
| CORRECTED HOWEVER AWG IS TILL SHOWN AS |
| #10. |
| |
| 4)NOTE: PLEASE SEE PLANS NOW HAVE NOTE |
| REMOVED ABOUT THERE BEING MAINS ON THE |
| OUTSIDE OF HOUSE? |
| |
| 5)NOTE: PLEASE SEE PLANS STILL HAVE SOME |
| LOCATIONS WHICH REQUIRE RECEPTS PER |
| 210.52 |
| |
| **NOTE** A SD WILL BE REQUIRED ON FIRST |
| FLR AT THE CLOSEST POSSIBLE LOCATION |
| TO THE VICINITY OF STAIRS. ONE HAS BEEN |
| NOTED ON ONE SET BUT LOCATION MAY BE |
| CHANGED DUE TO ARCH BLDG. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| THIS COMMENT OS FOR ALL TRADES IF SHEETS |
| NEED BE CHANGED OUT OR INSERTED INTO |
| SETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |