Plan Review Notes
Plan Review Notes For Permit 04061352
Permit Number 04061352
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-20 00:00:00*************** UNSAT *************
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEWS WERE NOT ADDRESSED COMPLETELY.
  
 1 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLANS INDICATE EST 118 RECESSED LTS, YET
 PANELS INDICATE 50 EACH PANEL?
 PLEASE ALSO SEE EACH PANEL SHOWS ALL
 50 LTS ON ONE CIRCUIT. THESE CIRCUITS
 ARE 15A #14. THESE LOADS MAY NOT BE ON
 ONLY TWO CIRCUITS.
  
 2)NOTE: PLEASE SEE LOAD CALCS FOR PANEL
 "C" WERE NOT CHANGED. PLEASE SEE ALL
 CONTINUOUS LOADS MUST BE FIGURED AT 125%
 220.14,430.24,25,26.
  
 3)NOTE: PLEASE SEE AHU #4 OCP HAS BEEN
 CORRECTED HOWEVER AWG IS TILL SHOWN AS
 #10.
  
 4)NOTE: PLEASE SEE PLANS NOW HAVE NOTE
 REMOVED ABOUT THERE BEING MAINS ON THE
 OUTSIDE OF HOUSE?
  
 5)NOTE: PLEASE SEE PLANS STILL HAVE SOME
 LOCATIONS WHICH REQUIRE RECEPTS PER
 210.52
  
 **NOTE** A SD WILL BE REQUIRED ON FIRST
 FLR AT THE CLOSEST POSSIBLE LOCATION
 TO THE VICINITY OF STAIRS. ONE HAS BEEN
 NOTED ON ONE SET BUT LOCATION MAY BE
 CHANGED DUE TO ARCH BLDG.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 THIS COMMENT OS FOR ALL TRADES IF SHEETS
 NEED BE CHANGED OUT OR INSERTED INTO
 SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]