2004-07-07 00:00:00 | *************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE 210.63 FOR MISSING |
| RECEPT FOR A/C UNITS. |
| |
| 2)NOTE: PLEASE VERIFY OCP FOR 7.5KW |
| AHU'S. SHOWN WITH 60A |
| |
| 3)NOTE: PLEASE CORRELATE PANEL "C" OCP |
| AND RATING. RISER SHOWS AS 50A AND |
| PANEL "B" SCHEDULE SHOWS 60A? |
| |
| 4)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| PLACEMENT. AREAS MARKED ON ONE SET OF |
| PLANS. PLEASE ALSO SEE RAIL AREAS ARE |
| ALSO CONSIDERED AS WALL SPACE. |
| |
| 5)NOTE: PLEASE SEE 210.52D , RECEPTS TO |
| BE W/IN 3' OF SINKS. |
| |
| 6)NOTE: SD TO BE MOVED INTO MASTER BEDRM |
| NFPA-72 8-1.4.1.6.2 |
| |
| 7 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 8 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 9)NOTE: PLEASE SEE PLANS INDICATE A |
| MAIN DISCONNECT OUTSIDE, YET RISER DOES |
| NOT SHOW THIS? PLEASE VERIFY THIS? |
| |
| 10)NOTE: PLEASE SEE 220.14, 430.24,25,26 |
| FOR LOAD CALCULATION TO FIGURED FOR |
| PANEL "C". |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |