Plan Review Notes
Plan Review Notes For Permit 04061350
Permit Number 04061350
Review Stop E
Sequence Number 7
Notes
Date Text
2005-12-07 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN
 WITH 20A OCP ON #14.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 FOR POOL PANEL AND PANEL "B"&"A"WITH
 RISER DIAGRAM.
 RISER SHOWS PANEL "B" FEEDING POOL
 PANEL, HOWEVER PANEL "A" SCHEDULE
 INDICATES POOL PANEL COMING FROM THIS
 LOCATION.
 PLEASE SEE PANEL "A" SHOWS 60A OCP AND
 #6 TO POOL PANEL. POOL PANEL ON RISER IS
 SHOWN AS 60A OCP AND #4.
 215.5
  
 3)NOTE: PLEASE SEE SD IN MASTER BEDRM
 AND OTHER LOCATIONS ARE ALL REQUIRED TO
 BE WITHIN 12"OF THE HIGHEST
 POINT OF A FLAT CEILING, AND WITHIN 3'
 OF THE PEAK ON A SLOPED CEILING.
 PLEASE KNOW, IF TRAY CEILING IS 12" OR
 MORE ABOVE OTHER CEILING IN RM, THE SD
 WILL BE REQUIRED TO BE LOCATED IN TRAY
 CEILING AREA.
 NFPA-72 11.8.3.5
  
 4)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # IN LOAD
 CALCS ETC.
 PLEASE SEE LOAD CALCS INDICATE A TOTAL
 OF 90, HOWEVER THERE ARE MORE ON PLANS
 PLEASE ADJUST.
 220.3B4
  
 5)NOTE: PLEASE SEE AHU#2 ON PANEL
 SCHEDULE WHICH INDICATES A 10KW HEAT,
 YET OCP IS SHOWN AT 50A'S. PLEASE SEE
 424.3 WHICH REUIRES A MIN 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]