Plan Review Notes
Plan Review Notes For Permit 04061350
Permit Number 04061350
Review Stop E
Sequence Number 6
Notes
Date Text
2005-10-21 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE CORRELATE ALL A/C
 MECHANICAL EQUIPMENT.
 PLEASE SEE PANEL SCHEDULES INDICATE FOUR
 A/C SYSTEMS, HOWEVER PLANS DO NOT SHOW
 FOUR COMPLETE SYSTEMS.
 PLEASE ALSO SEE A/C #3 IS NOTED FOR
 GARAGE, HOWEVER THIS SYSTEM IS SHOWN
 NEXT TO MASTER BR.
 PLEASE SEE OTHERS.
 PLEASE SEE LOADS FOR EACH PANEL THE
 LARGETS LOADS FOR A/C SYSTEMS ARE TO BE
 FIGURED USUALLY THE HEAT LOAD. IF ONLY
 THE COOLING LOAD IS INDICATED ON ONE
 PANEL, THEN COOLING LOAD MUST BE SHOWN.
 220
  
 2)NOTE: PLEASE SEE BOTH PANELS "A" AND
 "B" INDICATE BEING MLO.
 PLEASE SEE RISER SHOWS THESE AS MCB.
 PLEASE CORRELATE AND INDICATE MCB'S AS
 REQIRED 230.70
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 IS NOW SHOWN GOING TO SLAB, HOWEVER THIS
 SHOULD BE NOTED AS FOOTER STEEL. 250.50
  
 4)NOTE: PLEASE SEE LARGEST MOTOR LOADS
 AND CONTINUOUS LOADS IN POOL PANEL NEED
 TO BE SHOWN AT 125%.
 215.3,230.42
  
  
  
 ** NOTE ALL SD'S ARE TO BE INSTALLED
 WITH IN THE HIGHEST POINT OF A FLAT
 CEILING.
 PLEASE SEE THAT ALL SD'S ARE TO BE
 INSTALLED WITHIN 3' OF A SLOPED CEILING
 PEAK.
 PLEASE SEE MASTER BEDRM.
 PLEASE SEE BEDRM #4.
 PLEASE BE SURE TO VERIFY INSTALLATION IN
 FIELD.
 NFPA-72 8-1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]