Plan Review Notes For Permit 04061350 |
Permit Number |
04061350 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-04-20 00:00:00 | **** UNSAT **** | | | | | | | | 1)NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | UNIT. | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | TO FLOORS ABOVE AND IN THE VICINITY OF | | BEDROOMS. | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | A MIN OF 3' FROM BATHROOM DOORS AND | | KITCHENS. | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | | ** PLEASE SEE MISSING SD LEADING TO FLR | | ABOVE IN FIRST LEVEL IN THE VICINITY OF | | STAIRS. | | PLEASE SEE MISSING SD IN BEDRM #3. | | | | 2)NOTE: PLEASE SEE MISSING PANEL "C" | | FROM PLANS. | | | | 3)NOTE: PLEASE SEE "NOTE #2" ON GEN | | NOTES, IF SD'S ARE WIRED TO KIT/BATH | | LIGHTING CIRCUIT, THEN AFCI PROTECTION | | WOULD BE REQUIRED FOR THOSE CIRCUITS | | ALSO .210.12 2002 NEC | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|