2004-07-20 00:00:00 | ************ UNSAT *********** |
| |
| PLEASE SEE PLANS HAVE HAD CHANGES MADE |
| WHICH HAVE GENERATED SOME NEW COMMENTS. |
| |
| 1)NOTE: PLEASE SEE A COMPLETELY NEW |
| RISER DIAGRAM IS NOW BEING SUBMITTED |
| SHOW NEW MCB PANEL BEING MOUNTED NEXT TO |
| METER CAN W/ MAIN DISCONNECTS REMOVED. |
| PLEASE SEE PLANS INDICATE MCB INSIDE |
| GARAGE WHICH IS OK, HOWEVER MAY NOT BE |
| FED FROM THE SIDE OR OVERHEAD. |
| PLEASE SEE 230.70 WHICH REQUIRES MAIN |
| DISC'S AT NEAREST POINT OF ENTRANCE |
| INTO BLDG. LOCAL AMEND 230.70 LIMITS TO |
| NO MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| -S "INSIDE" BLDG. THIS MUST BE SHOWN AS |
| SLAB FED/UNDERGROUND. |
| PLEASE ALSO SEE EQUIPMENT GROUNDING |
| CONDUCTORS SHOWN FROM METER TO FIRST |
| MENAS OF DISC ARE NOT PERMITTED. |
| PLEASE SEE 250.24,250.6. EQP GRNDS ARE |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISC. |
| PLEASE SHOW LOCATION OF METER. |
| |
| 2)NOTE: PLEASE SEE OCP WAS CORRECTED FOR |
| AHU#3, YET AWG IS STILL SHOWN AS #10? |
| |
| 3)NOTE: PLEASE SEE RECEPTS HAVE BEEN |
| MOVED UPSTAIRS FROM ORIG PLANS. |
| PLEASE SEE 210.52/LOFT 6'FROM DOOR AND |
| 2' OF WALL IN BEDRM #3. WHICH WAS ON |
| FIRST SET. |
| |
| 4)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |