Plan Review Notes
Plan Review Notes For Permit 04061350
Permit Number 04061350
Review Stop E
Sequence Number 10
Notes
Date Text
2006-01-30 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE POOL PANEL, PLEASE
 VERIFY ALL OCP SHOWN AS MANY CIRCUITS
 INDICATE 2-POLE CIRCUITS FOR ITEMS WHICH
 DO APPEAR THEY SHOULD BE 220V, GAS
 HEATER?, POOL CHROLINATOR ETC.
 PLEASE ALSO SEE 5 CIRCUITS ARE SHOWN FOR
 WHAT APPEARS TO BE ONE POOL LT??
 215.5
  
 2)NOTE: PLEASE SEE PLANS INDICATE A 240V
 RECEPT FOR DRYER. PLEASE SEE PANEL
 SCHEDULE SHOWS THIS AS 1.5 KW, 20A, #12
 CIRCUIT??
 PLEASE KNOW, IF THIS IS GAS PLEASE
 INDICATE. PLEASE KNOW, 240V RECEPT
 PROVIDED FOR POSSIBLE "FUTURE" ELEC
 DRYER SHOULD BE INDICATED IN LOAD.
 220.18, 215.5
  
 3)NOTE: PLEASE SEE COOK-TOP IS SHOWN
 WITH 7.5 KW LOAD ON A 1-POLE , 20A
 BRANCH CIRCUIT. PLEASE VERIFY AND ADJUST
 OCP, AWG ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]