Plan Review Notes
Plan Review Notes For Permit 04061350
Permit Number 04061350
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-06 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. RISER SHOWS PANELS AS 150A'S
 AND FED W/ 200A BRKRS. PANEL SCHEDULE
 INDICATES 200A PANELS.
 215.5
  
 2)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE CONDUCTOR.
 400A SERVICE INDICATED.
  
 3)NOTE: PLEASE SEE OCP SHOWN FOR 7.5KW
 HEAT ON AHU #3,
  
 4)NOTE: PLEASE SEE PLANS DO NOT SHOW
 GFI RECEPT FOR WHIRLPOOL TUB AS SHOWN
 ON PANEL SCHEDULE.
  
 5)NOTE: PLEASE SEE 210.52C1-5 FOR RECEPT
 REQUIRED ALONG COUNTERSPACE. ?
  
 6)NOTE: PLEASE SEE 210.52 FOR RECEPT IN
 BEDRM #2
  
 7) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 8)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]