Plan Review Notes For Permit 04061317 |
Permit Number |
04061317 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) POOL LAYOUT SHOWS 8 INLETS, BUT POOL | | SPECIFICATIONS CALLS FOR 3 INLETS. ALSO | | WATER FEATURES INDICATE A 24" SPILLWAY, | | BUT SPA INFORMATION AT POOL LAYOUT DOES | | NOT INDICATE SPILLWAY. PLEASE CORRELATE | | PLANS AND SPECIFICATIONS. | | 2) SECOND SET OF POOL PLANS ARE NOT | | SIGNED, SEALED, AND DATED AS REQUIRED IN | | FS 471.025 AND FAC 62G25-34.002(1)(2). | | 3) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | A) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | C) FBC-2001 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|