Plan Review Notes
Plan Review Notes For Permit 04061317
Permit Number 04061317
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-31 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) POOL LAYOUT SHOWS 8 INLETS, BUT POOL
 SPECIFICATIONS CALLS FOR 3 INLETS. ALSO
 WATER FEATURES INDICATE A 24" SPILLWAY,
 BUT SPA INFORMATION AT POOL LAYOUT DOES
 NOT INDICATE SPILLWAY. PLEASE CORRELATE
 PLANS AND SPECIFICATIONS.
 2) SECOND SET OF POOL PLANS ARE NOT
 SIGNED, SEALED, AND DATED AS REQUIRED IN
 FS 471.025 AND FAC 62G25-34.002(1)(2).
 3) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 A) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 C) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]