2005-05-05 00:00:00 | REVISION DATED 3/30/05 |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| 1.) SHEET A1.1 SHOWS THE FREIGHT LIFT AS |
| REMAINING, S1 SHOWS THE LIFT REMOVED. |
| STRUCTURALS AND ARCHITECTURALS SHOULD BE |
| CONSISTENT. |
| |
| 2.)PROVIDE STAIR WIDTHS, FBC1004. |
| |
| 3.)DECLARE AN OCCUPANT LOAD, FBC TABLE |
| 1003.1. |
| |
| 4.)THE PRODUCT APPROVAL FOR THE |
| EXTERIOR DOOR AND THE ENERGY CALC HAVE |
| BEEN STAMPED AND A COPY RETAINED. |
| |
| 5.)SEE PREVIOUS LIST IN REGARDS TO |
| VERTICAL ACCESSIBILITY, FBC11-4.1.3. |
| HOW IS THIS BEING ADDRESSED? |
| |
| 6.)A 1 HR PROTECTED STAIR IS SHOWN |
| A1.0.PLEASE EXPLAIN HOW 1 HR IS |
| MAINTAINED THROUGH THE SECOND FLOOR. |
| SEE FBC1006.1.3.1, 705.1.2.OPENINGS |
| ARE SHOWN WITHOUT FIRE RESISTANCE |
| INFORMATION. |
| |
| 7.)A1.2, STAIR DETAILS HAS TWO DETAILS |
| WHICH ARE ILLEGIBLE. |
| |
| 8.)A HANDRAIL IN COMPLIANCE WITH |
| FBC1007.5 IS REQUIRED ON BOTH SIDES OF |
| THE STAIRS FBC1007.5.2.ONLY ONE IS |
| SHOWN. |
| |
| 9.)SHEET A1.2, AN EXIT CORRIDOR IS |
| SHOWN.WHERE IS THIS ON THE PLAN?IT |
| REFERS TO UL-U465; PROVIDE THIS DETAIL |
| ON THE PLAN. |
| |
| 10.) WHEN RESUBMITTING, PLEASE PROVIDE A |
| TRANSMITTAL SHEET EXPLAINING HOW THESE |
| ITEMS ARE BEING ADDRESSED. |
| |
| 11.)NOTE - STRUCTURALS SUBMITTED |
| SEPARATELY REVIEWED AGAIN AND PUT WITH |
| ARCHITECTURAL REVISION. |