Plan Review Notes
Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop B
Sequence Number 9
Notes
Date Text
2005-05-05 00:00:00REVISION DATED 3/30/05
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) SHEET A1.1 SHOWS THE FREIGHT LIFT AS
 REMAINING, S1 SHOWS THE LIFT REMOVED.
 STRUCTURALS AND ARCHITECTURALS SHOULD BE
 CONSISTENT.
  
 2.)PROVIDE STAIR WIDTHS, FBC1004.
  
 3.)DECLARE AN OCCUPANT LOAD, FBC TABLE
 1003.1.
  
 4.)THE PRODUCT APPROVAL FOR THE
 EXTERIOR DOOR AND THE ENERGY CALC HAVE
 BEEN STAMPED AND A COPY RETAINED.
  
 5.)SEE PREVIOUS LIST IN REGARDS TO
 VERTICAL ACCESSIBILITY, FBC11-4.1.3.
 HOW IS THIS BEING ADDRESSED?
  
 6.)A 1 HR PROTECTED STAIR IS SHOWN
 A1.0.PLEASE EXPLAIN HOW 1 HR IS
 MAINTAINED THROUGH THE SECOND FLOOR.
 SEE FBC1006.1.3.1, 705.1.2.OPENINGS
 ARE SHOWN WITHOUT FIRE RESISTANCE
 INFORMATION.
  
 7.)A1.2, STAIR DETAILS HAS TWO DETAILS
 WHICH ARE ILLEGIBLE.
  
 8.)A HANDRAIL IN COMPLIANCE WITH
 FBC1007.5 IS REQUIRED ON BOTH SIDES OF
 THE STAIRS FBC1007.5.2.ONLY ONE IS
 SHOWN.
  
 9.)SHEET A1.2, AN EXIT CORRIDOR IS
 SHOWN.WHERE IS THIS ON THE PLAN?IT
 REFERS TO UL-U465; PROVIDE THIS DETAIL
 ON THE PLAN.
  
 10.) WHEN RESUBMITTING, PLEASE PROVIDE A
 TRANSMITTAL SHEET EXPLAINING HOW THESE
 ITEMS ARE BEING ADDRESSED.
  
 11.)NOTE - STRUCTURALS SUBMITTED
 SEPARATELY REVIEWED AGAIN AND PUT WITH
 ARCHITECTURAL REVISION.