Plan Review Notes For Permit 04061232 |
Permit Number |
04061232 |
|
Review Stop |
P |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2005-04-23 00:00:00 | REVISION DENIED | | | | FROM PREVIOUS REVIEW: | | 5) CONDENSATE PIPING SUPPORTS ON SHEET | | A4.0 SHOWN AS EVERY 10 FEET. TABLE 408.5 | | INDICATES THAT PVC WILL BE SUPPORTED | | EVERY 4 FEET. - ALSO INDICATE THAT PVC | | SHALL BE PROTECTED FROM U.V. RAYS PER | | MANUF. INSTRUCTIONS. SECTION 104.2.1. | | 6) LETTERS FROM ARCHITECT AND ENGINEER | | SHALL BE SIGNED/SEALED/DATED/NOTOIZED | | AND HAVE TITLE BLOCK INFORMATION | | REQUIRED BY FLORIDA ADMINISTRATIVE CODE | | AND FLORIDA STATUTES. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|