2005-04-06 00:00:00****CORRECTIONS****
 VARIOUS DETAILS PREPARED BY BIJAN
 PARSSI, PE
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE FORMER ARCHITECT AND ENGINEER
 HAVE SUBMITTED LETTERS STATED THAT THEY
 ARE NO LONGER DOR/EOR OF THE PROJECT.
 JIM PAINE, ARCHITECT, HAS SUBMITTED NEW
 PLANS.IS BIJAN PARSSI, PE THE NEW EOR
 FOR THIS PROJECT?OR IS THIS DELEGATED
 ENGINEERING?IF THIS IS DELEGATED
 ENGINEERING, THE DETAILS ARE TO BE
 REVIEWED BY DOR.IF HE IS THE NEW EOR,
 SUBMIT A LETTER STATING THIS AS ALL
 STRUCTURALS TO DATE HAVE BEEN SUBMITTED
 BY JIM PAINE.
  
 2.)THE COLUMN CONNECTION PLAN IS NOT
 SEALED.
  
 3.)AS PER CONVERSATION WITH THE
 CONTRACTOR, THE COLUMN CONNECTION PLAN
 IS SHOWING A C CHANNEL AND A STEEL
 COLUMN.THE DIMENSION 4X4X4 IS
 CONFUSING, IMPLIES A HEIGHT OF 4" RATHER
 THAN A COLUMN THE FULL HEIGHT.THE C
 CHANNEL IS SHOWN GRAPHICALLY BUT NOT
 SPECIFIED, WHAT SIZE?THE ANCHORING OF
 THE STEEL COLUMN AND C CHANNEL IS NOT
 SPECIFIED.ANCHORING AT THE BOTTOM OF
 THE COLUMN IS SPECIFIED, ASSUMING TO
 EXISTING SLAB ON 1ST FLOOR AS A CONCRETE
 ANCHOR IS SPECIFIED.IS THERE A BASE
 PLATE FOR THE COLUMN?SPECIFY WHERE
 THIS DETAIL IS TO BE USED.
  
  