Plan Review Notes
Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop P
Sequence Number 5
Notes
Date Text
2005-03-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 BUILDING
  
 1) SUBMIT A DETAIL FOR ACCESSIBLE BATH-
 ROOMS PER SECTIONS 11-4.16, 11-4.19, 11-
 4.21, 11-4.22 AND ALL SUBSECTIONS.
 2) SHT A3.2 THE SANITARY RISER DIAGRAM
 DOES NOTMEET CODE REQUIREMENTS. THE
 SERVICE SINK SHALL DISCHARGE DOWNSTREAM
 OF THE BATHROOM FIXTRUES. SECTION 909.1
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 4) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. SUBMIT DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS.
 5) SUBMIT DETAIL FOR CONDENSATE PIPING.
 SHOW PIPE SIZE, MATERIAL, SUPPORT DETAIL
 & TERMINATION POINT. SECTION 104.3.1.1.
 6) PLANS NOT HAVE A NEW ARCHITECT OF
 RECORD, AND PLANS PREVIOUSLY SUBMITTED
 FOR PLUMBING WERE SIGNED/SEALED/DATED BY
 AN ENGINEER. PLEASE SUBMIT A
 SIGNED/SEALED/DATED NOTORIZED LETTER FOR
 CHANGING ARCHITECTS AND REMOVING THE
 ENGINEER OF RECORD FROM THIS JOB. PLEASE
 SUBMIT TWO COMPLETE SETS OF PLANS FOR
 REVIEW AND FOR PUBLIC RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692