Date |
Text |
2005-03-01 00:00:00 | *********UNSAT******* |
| |
| PLEASE SEE PREVIOUS REVIEW NOTES FOR |
| ITEMS REDLINED REQUESTING," IF THERE ARE |
| ANY REVISIONS, PLEASE MAKE CORRECTIONS |
| TO PLANS AT THAT TIME". PLEASE SEE NOTES |
| FROM PREVIOUS REVIEW BELOW. |
| |
| |
| |
| 1)NOTE: PLEASE SEE PLANS NOW HAVE A NEW |
| ARCHITECT OF RECORD. |
| PLEASE SUBMIT A SIGNED/SEALED NOTORIZED |
| LETTER FOR CHANGING ARCH AND ENGINEER |
| FROM EACH PERSON. |
| PLEASE SEE NEW ARCHITECT MUST SUBMIT |
| COMPLETE SETS OF PLANS SIGNED AND SEALED |
| FOR COMPLETE SCOPE OF WORK. |
| |
| |
| PLEASE SEE BELOW WAS REDLINED ON |
| ORIGINAL PLANS AND SHOULD BE ADDRESSED |
| AT THIS TIME WHEN PLANS ARE DONE. |
| |
| 1)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| CONDUCTOR STILL NOT SHOWN PER 250.66. |
| TWO SETS OF 3/0'S,,,, 1/0 MIN GEC. |
| |
| |
| 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT |
| GROUNDING CONDUCTOR IS NOW ADDED FROM |
| METER TO MAIN? AN EQUIPMENT GRND IS NOT |
| INSTALLED UNTIL AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| 250.6, 250.24 |
| |
| |
| 3)NOTE: PLEASE SEE REDLINED EM/EXT LT |
| PER |
| 700.12E. |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |