Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop E
Sequence Number 5
Notes
Date Text
2005-03-01 00:00:00*********UNSAT*******
  
 PLEASE SEE PREVIOUS REVIEW NOTES FOR
 ITEMS REDLINED REQUESTING," IF THERE ARE
 ANY REVISIONS, PLEASE MAKE CORRECTIONS
 TO PLANS AT THAT TIME". PLEASE SEE NOTES
 FROM PREVIOUS REVIEW BELOW.
  
  
  
 1)NOTE: PLEASE SEE PLANS NOW HAVE A NEW
 ARCHITECT OF RECORD.
 PLEASE SUBMIT A SIGNED/SEALED NOTORIZED
 LETTER FOR CHANGING ARCH AND ENGINEER
 FROM EACH PERSON.
 PLEASE SEE NEW ARCHITECT MUST SUBMIT
 COMPLETE SETS OF PLANS SIGNED AND SEALED
 FOR COMPLETE SCOPE OF WORK.
  
  
 PLEASE SEE BELOW WAS REDLINED ON
 ORIGINAL PLANS AND SHOULD BE ADDRESSED
 AT THIS TIME WHEN PLANS ARE DONE.
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR STILL NOT SHOWN PER 250.66.
 TWO SETS OF 3/0'S,,,, 1/0 MIN GEC.
  
  
 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW ADDED FROM
 METER TO MAIN? AN EQUIPMENT GRND IS NOT
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT.
 250.6, 250.24
  
  
 3)NOTE: PLEASE SEE REDLINED EM/EXT LT
 PER
 700.12E.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  