2005-03-24 00:00:00 | PERMIT #04061232 |
| |
| ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| 1.)TYPE IV IS DECLARED ON THE COVER |
| SHEET.WOOD COLUMNS ARE SHOWN ON A1.0. |
| ALSO A1.0 STATES THAT THE FLOOR FINISH |
| IS WOOD, BUT A1.1 NOTES AN EXISTING WOOD |
| DECK.IS THE WOOD FLOOR NOTED A FLOOR |
| FINISH OR THE FLOOR FRAMING?OUR PLANS |
| CURRENTLY ON FILE SHOW WOOD JOISTS FOR |
| THE FLOOR FRAMING.SEE FBC606 REGARDING |
| DEFINITION OF TYPE IV BUILDING. |
| |
| 2.)THE COVER SHEET SHOWS 5739 SF FOR |
| FIRST FLOOR TWICE.PLEASE NOTE SECOND |
| FLOOR SQUARE FOOTAGE. |
| |
| 3.)SHEET A1.0 HAS A NOTE REGARDING A 1 |
| HOUR SEPARATION.WHAT IS THE PURPOSE OF |
| THIS SEPARATION?HOW WILL THE 1 HOUR |
| SEPARATION BE MAINTAINED WHERE THE WOOD |
| COLUMNS MEET THE BOTTOM OF THE FLOOR |
| CEILING ASSEMBLY?A FREIGHT LIFT IS |
| SHOWN ON A1.0; PROVIDE 1 HR FIRE RATING |
| INFORMATION. |
| |
| 4.)SHEET A1.0 BOTTOM RIGHT CORNER OF |
| PLAN SHOWS 1HR ENCLOSURE (SEE DETAIL). |
| NO DETAIL PROVIDED AND IT IS UNCLEAR HOW |
| THE 1 HR SEPARATION IS MAINTAINED |
| BETWEEN THE FIRST AND SECOND FLOORS AS |
| THE FLOOR PLAN SHOWS A WALL WHICH DOES |
| NOT ENCLOSE THE STAIRS. |
| |
| 5.)THERE IS A NOTE ON SHEET A1.3 THAT |
| ALL EXTERIOR OPENINGS ARE EXISTING. |
| OPENINGS AFFECTED BY THE SCOPE OF WORK |
| ON THIS PERMIT ARE TO BE CODE COMPLIANT |
| AND SHOW COMPLIANCE ON THE PLAN.ALSO |
| THERE IS A NEW DOOR SHOWN. |
| |
| 6.)PLEASE SEE FBC1006.1.3.2.IF THIS |
| BUILDING IS A TYPE V, THE STAIRWAY AT |
| THE TOP LEFT IS TO HAVE 3 HR PROTECTION. |
| |
| 7.)BASED ON PROPERTY APPRAISER?S |
| VALUATION, THIS IS AN OVER 50% |
| IMPROVEMENT, FBC3401.7.2.6. |
| |
| 8.)OPENINGS IN THE EXIT STAIR ARE |
| PROHIBITED EXCEPT AS NOTED IN |
| FBC1006.1.3.1 (WINDOW SHOWN IN |
| STAIRWAY). |
| |
| 9.)SHOW OPENING PROTECTIVES FOR THE |
| STAIRS AS REQUIRED BY FBC TABLE 705.1.2. |
| |
| 10.)DOOR 2, 1ST FLOOR, DOES NOT APPEAR |
| TO LEAD ANYWHERE.IF IT IS AN OPENING |
| INTO THE STAIR, INDICATE OPENING |
| PROTECTIVE REQUIREMENT. |
| |
| 11.) PROVIDE TEST REPORTS AND FLORIDA |
| STATE OR LOCAL PRODUCT APPROVAL FOR THE |
| NEW EXTERIOR DOOR. |
| |
| 12.) PROVIDE GUARDRAIL AND HANDRAIL |
| DETAILS.NOTE DESIGN CRITERIA IN |
| COMPLIANCE WITH FBC1608.1.1 (HANDRAIL) |
| AND FBC 1608.2.2 (GUARDRAIL).COMPLY |
| WITH ALL REQUIREMENTS OF FBC CHAPTERS 10 |
| AND 11. |
| |
| 13.) PROVIDE ACCESSIBILITY DETAILS; |
| ACCESSIBLE ENTRY, BATHROOM DETAILS |
| INCLUDING DIMENSIONS FOR GRAB BARS, LAV, |
| WC FBC CHAPTER 11. |
| |
| 14.) PROVIDE LOADING INFORMATION FOR |
| ROOFTOP MECHANICAL EQUIPMENT, DESIGN |
| LOAD LIMITATIONS OF EXISTING ROOF. |
| |
| 15.) ENERGY CALCS REQUIRED, FBC13. |
| |
| 16.) VERTICAL ACCESSIBILITY REQUIRED, |
| FBC11-4.1.3. |
| |
| 17.) PROVIDE DESIGN PRESSURES FOR THE |
| EXTERIOR DOOR AND DESIGN CRITERIA |
| FBC1606.1.7. |
| |
| 18.) DMP REVIEW REQUIRED.WHEN |
| RESUBMITTING, PLEASE INDICATE THAT A |
| ZONING REVIEW IS REQUIRED ON THE |
| RESUBMITTAL SHEET TO HELP EXPEDITE PLAN |
| REVIEW. |