Plan Review Notes For Permit 04061232 |
Permit Number |
04061232 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-11-29 00:00:00 | ***** PLANS REDLINED ****** | | | | 1)NOTE: PLEASE SEE GROUNDING ELECTRODE | | CONDUCTOR STILL NOT SHOWN PER 250.66. | | TWO SETS OF 3/0'S,,,, 1/0 MIN GEC. | | | | | | 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT | | GROUNDING CONDUCTOR IS NOW ADDED FROM | | METER TO MAIN? AN EQUIPMENT GRND IS NOT | | INSTALLED UNTIL AFTER THE FIRST MEANS OF | | DISCONNECT. | | 250.6, 250.24 | | | | | | ** BOTH OF THE ABOVE WERE REDLINED ON | | PLANS. IF ANY REV'S ARE MADE TO PLANS, | | PLEASE ALSO CORRECT THE ABOVE AT THAT | | TIME. *** | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|