Plan Review Notes
Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop E
Sequence Number 4
Notes
Date Text
2004-11-29 00:00:00***** PLANS REDLINED ******
  
 1)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR STILL NOT SHOWN PER 250.66.
 TWO SETS OF 3/0'S,,,, 1/0 MIN GEC.
  
  
 2)NOTE: PLEASE ALSO SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW ADDED FROM
 METER TO MAIN? AN EQUIPMENT GRND IS NOT
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT.
 250.6, 250.24
  
  
 ** BOTH OF THE ABOVE WERE REDLINED ON
 PLANS. IF ANY REV'S ARE MADE TO PLANS,
 PLEASE ALSO CORRECT THE ABOVE AT THAT
 TIME. ***
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]