2004-10-25 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTE#4 FROM PREVIOUS
 REVIEW. A GROUNDING ELECTRODE SYSTEM
 IS NOW SHOWN, HOWEVER SIZING OF GEC IS
 TO BE SIZED FOR THE PARALLEL 4/0'S
 PER 250.66. SHOWS A #3, WHICH IS NOT
 LARGE ENOUGH.
  
 2)NOTE : PLEASE SEE NOTE # 5FROM
 PREVIOUS REVIEW. PLEASE SEE MISSING
 LICENSE # FOR FIRM ONA-SHEETS.
 PLEASE SEE FAC 61G1-16.004 AND FS 481.-
 .219.
 THIS IS REQUIRED, WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SEE LOAD FOR WASHER/DRYER
 IS SHOWN AS 7KW ON A 2P-30A BRKR FOR
 OCP.
 PLEASE ALSO SEE 11KW LOAD SHOWN ON A
 2P-30A BRKR FOR ELEVATOR.
  
 4)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN TO PANEL
 AND FROM PANEL A TO B.
 250.110,250.122
  
 5)NOTE: PLEASE SEE MAIN DISCONNECT IS
 SHOWN AS MLO. APPEARS TO BE A MISPRINT??
  
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND INSERT NEW SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE SUBMITT
 -ED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]