2004-10-25 00:00:00 | ********* UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE NOTE#4 FROM PREVIOUS |
| REVIEW. A GROUNDING ELECTRODE SYSTEM |
| IS NOW SHOWN, HOWEVER SIZING OF GEC IS |
| TO BE SIZED FOR THE PARALLEL 4/0'S |
| PER 250.66. SHOWS A #3, WHICH IS NOT |
| LARGE ENOUGH. |
| |
| 2)NOTE : PLEASE SEE NOTE # 5FROM |
| PREVIOUS REVIEW. PLEASE SEE MISSING |
| LICENSE # FOR FIRM ONA-SHEETS. |
| PLEASE SEE FAC 61G1-16.004 AND FS 481.- |
| .219. |
| THIS IS REQUIRED, WHEATHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| |
| 3)NOTE: PLEASE SEE LOAD FOR WASHER/DRYER |
| IS SHOWN AS 7KW ON A 2P-30A BRKR FOR |
| OCP. |
| PLEASE ALSO SEE 11KW LOAD SHOWN ON A |
| 2P-30A BRKR FOR ELEVATOR. |
| |
| 4)NOTE: PLEASE CLARIFY MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAIN TO PANEL |
| AND FROM PANEL A TO B. |
| 250.110,250.122 |
| |
| 5)NOTE: PLEASE SEE MAIN DISCONNECT IS |
| SHOWN AS MLO. APPEARS TO BE A MISPRINT?? |
| |
| |
| PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND INSERT NEW SHEETS INTO COMPLETED |
| SETS FOR REVIEW AND STAMPING. |
| ONE COPY OF OLD SHEETS SHOULD BE SUBMITT |
| -ED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |