Plan Review Notes
Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop P
Sequence Number 2
Notes
Date Text
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
  
 1) FAC 61G1-16.003 THE SIGNATURE AND
 DATE ARE REQUIRED ON THE PERSONAL SEAL
 OF THE ARCHITECT. - NO DATE SHOWN. FS
 481.2055
 2) FAC 61G1-16.004(2) THE FIRM LICENSE
 (CERTIFICATE OF AUTHORIZATION) NUMBER IS
 REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FS 481.219
 3) ARE BOTH FLOORS A SINGLE OCCUPANCY OF
 ONE TENANT? IF NOT A DRINKING FOUNTAIN
 OR BOTTLED WATER COOLER SHALL BE REQUIR-
 ED IN EACH SPACE. TABLE 403.1
 4) REMOVE ALL VOIDED SHEETS AND SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]