Plan Review Notes
Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-01 00:00:00********* UNSAT *************
  
 PLEASE SEE THE FOLLOWING FOR SOME NOTES
 FROM FIRST REVIEW WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATEW/ PANEL SCHEDULE.
 PLEASE SEE EM LTS/700.12E
  
 2)NOTE: PLEASE SEE 210.63 AND VERIFY
 GFI LOCATION FOR RTU.
  
 3)NOTE: PLEASE SEE LOAD CALCS ARE NOW
 SUBMITTED HOWEVER, ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 215.3,230.42,ETC
  
 4)NOTE: PLEASE SEE 250.50 FOR GROUNDING
 ELECTRODE SYSTEM.
 NOT SHOWN.
  
 5)NOTE: PLEASE SEE FS 481.219 AND FAC
 61G1-16.004.
 PLEASE INCLUDE ALL REQUIRED LICENSE
 #'S ON TITLE BLOCKS.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWER
 'S.
  
 6)NOTE: PLEASE SEE ATTACHED COPY OF
 FS553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS ONLY A NOTICE AT THIS TIME.
  
 ***PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 DO NOT ATTACH OLD SHEETS TO PLANS.
 THESE MAY BE PLACE IN A SEPARATE ROLL
 FOR REFERENCE ONLY.
  
 PLEASE SEE OTHER COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]