2004-09-01 00:00:00 | ********* UNSAT ************* |
| |
| PLEASE SEE THE FOLLOWING FOR SOME NOTES |
| FROM FIRST REVIEW WERE NOT ADDRESSED. |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATEW/ PANEL SCHEDULE. |
| PLEASE SEE EM LTS/700.12E |
| |
| 2)NOTE: PLEASE SEE 210.63 AND VERIFY |
| GFI LOCATION FOR RTU. |
| |
| 3)NOTE: PLEASE SEE LOAD CALCS ARE NOW |
| SUBMITTED HOWEVER, ALL CONTINUOUS LOADS |
| ARE TO BE SHOWN AT 125%. |
| 215.3,230.42,ETC |
| |
| 4)NOTE: PLEASE SEE 250.50 FOR GROUNDING |
| ELECTRODE SYSTEM. |
| NOT SHOWN. |
| |
| 5)NOTE: PLEASE SEE FS 481.219 AND FAC |
| 61G1-16.004. |
| PLEASE INCLUDE ALL REQUIRED LICENSE |
| #'S ON TITLE BLOCKS. |
| THIS IS REQUIRED ON ALL SHEETS WHEATHER |
| OR NOT COMMENT IS MADE BY OTHER REVIEWER |
| 'S. |
| |
| 6)NOTE: PLEASE SEE ATTACHED COPY OF |
| FS553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONAL. |
| THIS IS ONLY A NOTICE AT THIS TIME. |
| |
| ***PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| DO NOT ATTACH OLD SHEETS TO PLANS. |
| THESE MAY BE PLACE IN A SEPARATE ROLL |
| FOR REFERENCE ONLY. |
| |
| PLEASE SEE OTHER COMMENTS. |
| |