2005-05-19 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)TWO SETS OF PLANS SUBMITTED. |
| PLEASE COLLATE SHEETS INTO ONE SET FOR |
| REVIEW/ISSUANCE. |
| |
| 2.)THE UL DETAIL REQUESTED HAS NOT |
| BEEN INCORPORATED INTO THE PLAN AS |
| REQUESTED BY THE PREVIOUS REVIEW.A |
| PHOTOCOPY OF THE UL ASSEMBLY HAS BEEN |
| PROVIDED FOR YOU; PLEASE STAPLE INTO THE |
| PLAN.HOWEVER IN THE FUTURE A FIRE |
| SEPARATION IS TO INCLUDE A DETAIL, NOT |
| JUST A UL REFERENCE NUMBER. |
| |
| |
| |
| ****PROVISO**** |
| |
| ***PROVIDE AFFIDAVIT***FBC106.4.2 (RE |
| STORAGE OCCUPANCY). IT SHALL BE THE |
| RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPIETOR OR OCCUPANT OF GROUP S AND |
| GROUP F OCCUPANCIES, OR ANY OCCUPANCY |
| WHERE EXCESSIVE FLOOR LOADING IS LIKELY |
| TO OCCUR, TO EMPLOY A COMPETENT |
| ARCHITECT OR ENGINEER IN COMPUTING THE |
| SAFE FLOOR LOAD CAPACITY. ALL SUCH |
| COMPUTATIONS SHALL BE ACCOMPANIED BY AN |
| AFFADAVIT FROM THE ARCHITECT OR ENGINEER |
| STATING THE SAFE ALLOWABLE FLOOR LOADS |
| ON EACH FLOOR IN POUNDS PER SQ FT.THE |
| COMPUTATIONS & AFFADAVIT SHALL BE FILED |
| AS A PERMANENT RECORD OF THE BLDG DEPT. |
| |
| ***PROVIDE SIGNAGE***FBC106.4.3.SIGNS |
| REQUIRED. IN EVERY BUILDING OR PART OF A |
| BUILDING USED FOR STORAGE, INDUSTRIAL OR |
| HAZARDOUS PURPOSES, THE SAFE FLOOR |
| LOADS, AS REVIEWED BY THE BUILDING |
| OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| PLATES OF APPROVED DE SIGN WHICH SHALL |
| BE SUPPLIED & SECURELY AFFIXED BY THE |
| OWNER OF THE BUILDING IN A CONSPICUOUS |
| PLACE IN EACH STORY TO WHICH THEY |
| RELATE. SUCH PLATES SHALL NOT BE REMOVED |
| OR DEFACED, & IF LOST, REMOVED THE OWNER |
| OF THE BUILDING SHALL REPLACE THEM. |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |