Plan Review Notes
Plan Review Notes For Permit 04061232
Permit Number 04061232
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 BUILDING
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES FOR FIXTURES PER TABLES 1103.1
 (BLDG.) AND 403.1 (PLUMB.) SHOW SQUARE
 FOOTAGE FOR EACH OCCUPANCY, BUSINESS,
 INDUSTRIAL, & STORAGE.
 2) INDICATE TYPE AND AMOUNT OF MATERIALS
 TO BE STORED. RESPONSE MAY CREATE NEW
 COMMENTS. SECTION 104.2.1
 3) WHAT TYPE OF BUSINESS/WORK WILL BE
 DONE IN THIS SPACE?
 4) PRIVATE BATHROOM SHALL BE ADAPTABLE.
 SUBMIT A DETAIL SHOWING BACKING FOR W/C
 GRAB BARS, SIZE OF OPENING FOR W/C, THE
 BACKING FOR GRAB BARS FOR THE SHOWER,
 CONTROL AREA FOR SHOWER, HEIGHT OF SEAT
 AND BACKING FOR SEAT, & CURB HEIGHT.
 SECTION 11-4.1.3(11).- ALSO INDICATE
 TURNING AREA IN ADAPTABLE BATHROOM.
 5) SUBMIT A DETAIL FOR ACCESSIBLE BATH-
 ROOMS PER SECTIONS 11-4.16, 11-4.19, 11-
 4.21 AND ALL SUBSECTIONS.
 6) DOORS REQUIRED TO BE ACCESSIBLE SHALL
 COMPLY WITH THE REQUIREMENTS OF 11-4.13.
 AND 11-4.13.5. THE CLEAR WIDTH OF 32"
 CAN NOT BE ACHIEVED WITH A 2'8" DOOR.
 7) LUNCH ROOM SINK SHALL BE ACCESSIBLE
 PER SECTION 11-4.24. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH THIS SECTION AND
 ALL SUBSECTIONS.
 8) SHT PO-01 WATER RISER DIAGRAM & NOTES
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM RISER AND NOTES. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9, (AT
 ICE MAKERS, WASH MACHINES, & DISHWASHERS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE PER PDI-WH 201 AND
 MANUF. - RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THERE ARE FIXTURES NOT
 SHOWN ON FLOOR PLAN, (TUB & LAV).
 9) SHT P0-01 THE SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOT
 DOES IT MEET CODE REQUIREMENTS. W/C'S
 (A) W/C'S SHALL NOT BE DOUBLE TRAPPED.
 SECTION 1002.1. W/C'S HAVE AN INTEGRAL
 TRAP. SEE EXCEPTION (1).
 (B) SANITARY CROSS FITTINGS ARE NOT
 APPROVED FOR UNDERGROUND USE. SECTION
 706.3.
 (C) HORIZONTAL DRY VENTS ARE NOT APPRO-
 VED PER SECTION 905.3
 (D) TEE FITTINGS ARE NOT APPROVED FOR
 USE AS SHOWN AT THE TOP OF RISER WITH
 DRAINAGE FROM BOTH DIRECTIONS. TABLE
 706.3.
 (E) NO BATH TUB IN ROOM 206 SHOWN ON
 THE FLOOR PLAN. SECTION 104.2.1
 (F) 2 LAVS SHOWN ON RISER, BUT ONLY ONE
 SHOWN ON FLOOR PLAN. SECTION 104.2.1.
 (G) WASH MACHINE REQUIRES A TRAP AND A
 STANDPIPE. SECTIONS 1002.1, & 802.4.
 (H) DISHWASHERS REQUIRE AN AIR GAP FIT-
 TING ABOVE THE FLOOR RIM LEVEL OF THE
 SINK.
 (I) WHAT IS THE FIXTURE BETWEEN THE
 DISHWASHER AND THE SINK IN THE LUNCHROOM
 WHAT IS THE USAGE OF THIS FIXTURE. SECT-
 ION 104.2.1.
 (J) THE RISER DIAGRAM SHALL REFLECT THE
 LAYOUT OF THE FIXTURES ON THE FLOOR PLAN
 AND THE ACTUAL INSTALLATION OF THE PIP-
 ING. SEE RED LINE CORRECTIONS AND EXAMP-
 LE.
 10) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 11) THERMAL EXPANSION CONTROL IS REQUIR-
 ED PER SECTION 607.3.2
 12) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS