Date |
Text |
2004-07-14 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| FBC-2001 BUILDING |
| |
| 1) SUBMIT CALCULATIONS FOR MINIMUM FAC- |
| ILITIES FOR FIXTURES PER TABLES 1103.1 |
| (BLDG.) AND 403.1 (PLUMB.) SHOW SQUARE |
| FOOTAGE FOR EACH OCCUPANCY, BUSINESS, |
| INDUSTRIAL, & STORAGE. |
| 2) INDICATE TYPE AND AMOUNT OF MATERIALS |
| TO BE STORED. RESPONSE MAY CREATE NEW |
| COMMENTS. SECTION 104.2.1 |
| 3) WHAT TYPE OF BUSINESS/WORK WILL BE |
| DONE IN THIS SPACE? |
| 4) PRIVATE BATHROOM SHALL BE ADAPTABLE. |
| SUBMIT A DETAIL SHOWING BACKING FOR W/C |
| GRAB BARS, SIZE OF OPENING FOR W/C, THE |
| BACKING FOR GRAB BARS FOR THE SHOWER, |
| CONTROL AREA FOR SHOWER, HEIGHT OF SEAT |
| AND BACKING FOR SEAT, & CURB HEIGHT. |
| SECTION 11-4.1.3(11).- ALSO INDICATE |
| TURNING AREA IN ADAPTABLE BATHROOM. |
| 5) SUBMIT A DETAIL FOR ACCESSIBLE BATH- |
| ROOMS PER SECTIONS 11-4.16, 11-4.19, 11- |
| 4.21 AND ALL SUBSECTIONS. |
| 6) DOORS REQUIRED TO BE ACCESSIBLE SHALL |
| COMPLY WITH THE REQUIREMENTS OF 11-4.13. |
| AND 11-4.13.5. THE CLEAR WIDTH OF 32" |
| CAN NOT BE ACHIEVED WITH A 2'8" DOOR. |
| 7) LUNCH ROOM SINK SHALL BE ACCESSIBLE |
| PER SECTION 11-4.24. SUBMIT A DETAIL |
| SHOWING COMPLIANCE WITH THIS SECTION AND |
| ALL SUBSECTIONS. |
| 8) SHT PO-01 WATER RISER DIAGRAM & NOTES |
| AIR CHAMBERS ARE NOT APPROVED. DELETE |
| FROM RISER AND NOTES. WATER HAMMER ARR- |
| ESTORS REQUIRED BY SECTION 604.9, (AT |
| ICE MAKERS, WASH MACHINES, & DISHWASHERS |
| SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE PER PDI-WH 201 AND |
| MANUF. - RISER DIAGRAM DOES NOT REFLECT |
| THE FLOOR PLAN. THERE ARE FIXTURES NOT |
| SHOWN ON FLOOR PLAN, (TUB & LAV). |
| 9) SHT P0-01 THE SANITARY RISER DIAGRAM |
| DOES NOT REFLECT THE FLOOR PLAN, NOT |
| DOES IT MEET CODE REQUIREMENTS. W/C'S |
| (A) W/C'S SHALL NOT BE DOUBLE TRAPPED. |
| SECTION 1002.1. W/C'S HAVE AN INTEGRAL |
| TRAP. SEE EXCEPTION (1). |
| (B) SANITARY CROSS FITTINGS ARE NOT |
| APPROVED FOR UNDERGROUND USE. SECTION |
| 706.3. |
| (C) HORIZONTAL DRY VENTS ARE NOT APPRO- |
| VED PER SECTION 905.3 |
| (D) TEE FITTINGS ARE NOT APPROVED FOR |
| USE AS SHOWN AT THE TOP OF RISER WITH |
| DRAINAGE FROM BOTH DIRECTIONS. TABLE |
| 706.3. |
| (E) NO BATH TUB IN ROOM 206 SHOWN ON |
| THE FLOOR PLAN. SECTION 104.2.1 |
| (F) 2 LAVS SHOWN ON RISER, BUT ONLY ONE |
| SHOWN ON FLOOR PLAN. SECTION 104.2.1. |
| (G) WASH MACHINE REQUIRES A TRAP AND A |
| STANDPIPE. SECTIONS 1002.1, & 802.4. |
| (H) DISHWASHERS REQUIRE AN AIR GAP FIT- |
| TING ABOVE THE FLOOR RIM LEVEL OF THE |
| SINK. |
| (I) WHAT IS THE FIXTURE BETWEEN THE |
| DISHWASHER AND THE SINK IN THE LUNCHROOM |
| WHAT IS THE USAGE OF THIS FIXTURE. SECT- |
| ION 104.2.1. |
| (J) THE RISER DIAGRAM SHALL REFLECT THE |
| LAYOUT OF THE FIXTURES ON THE FLOOR PLAN |
| AND THE ACTUAL INSTALLATION OF THE PIP- |
| ING. SEE RED LINE CORRECTIONS AND EXAMP- |
| LE. |
| 10) AN RPZ BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE. SECTION 608.13.2 |
| 11) THERMAL EXPANSION CONTROL IS REQUIR- |
| ED PER SECTION 607.3.2 |
| 12) A PROFESSIONAL ENGINEER SHALL SIGN |
| HIS NAME AND AFFIX HIS SEAL TO ALL PLANS |
| SPECIFICATIONS, REPORTS AND FINAL BID |
| DOCUMENTS PROVIDED TO THE OWNER OR THE |
| OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| MENTS PREPARED OR ISSUED BY SAID REGIS- |
| TRANT AND BEING FILED FOR PUBLIC RECORD. |
| THE DATE THAT THE SIGNATURE AND SEAL IS |
| AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| UNDER THE SIGNATURE OF THE PROFESSIONAL |
| ENGINEER, FAC 61G15-23.002(1) |
| FS 471.025 |
| EACH SHEET OF PLANS AND PRINTS WHICH |
| MUST BE SEALED UNDER THE PROVISIONS OF |
| CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN |
| RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| FS 471.025 |
| ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| SHEET. IF PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL |
| AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING |
| BUSINESS ON EACH SHEET. A TITLE BLOCK |
| WILL SATISFY THIS REQUIREMENT. FAC |
| 61G15-23.002(2) - FS 471.025 |
| |
| REVIEW BY KEN STEVENS |