2004-06-25 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS
 APPEAR TO BE SHOWN ON A-SHEETS LABELED
 AS REFLECTED CEILING PLANS??
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. 215.5
 PLEASE ALSO SEE 700.12E
  
 5)NOTE: PLEASE SEE PLANS MUST CONTAIN
 LEGAL SIGNATURE AS SHOWN ON SEAL.
 PLANS APPEAR TO CONTAIN INITIALS.
 IF THIS IS INDEED "LEGAL" SIGNATURE,
 PLEASE PROVIDE A COMPLETED SIGNED, DATED
 AND SEALED NOTORIZED LETTER. PLEASE BE
 SURE NOTORY INCLUDES ALL INFORMATION AS
 REQUIRED.
 PLEASE SEE FS 481.221, WHICH REQUIRES
 SIAGNTURE.
  
 6)NOTE: PLEASE SEE FAC 61G1-16.004,
 AND FS 481.219.
 PLEASE INCLUDE ALL LICENSE #'S ON TITLE
 BLOCK AS REQUIRED PER ABOVE.
  
 7)NOTE: PLEASE INCLUDE GROUNDING ELEC-
 -TRODE SYSTEM. 250.50. NO DETAIL GIVEN.
  
 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON
 PLANS AND DISC'S PER 440.11
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]