2004-06-25 00:00:00 | ************* UNSAT ************* |
| |
| 1)NOTE: PLEASE SEE ELECTRICAL PLANS |
| APPEAR TO BE SHOWN ON A-SHEETS LABELED |
| AS REFLECTED CEILING PLANS?? |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. 215.5 |
| PLEASE ALSO SEE 700.12E |
| |
| 5)NOTE: PLEASE SEE PLANS MUST CONTAIN |
| LEGAL SIGNATURE AS SHOWN ON SEAL. |
| PLANS APPEAR TO CONTAIN INITIALS. |
| IF THIS IS INDEED "LEGAL" SIGNATURE, |
| PLEASE PROVIDE A COMPLETED SIGNED, DATED |
| AND SEALED NOTORIZED LETTER. PLEASE BE |
| SURE NOTORY INCLUDES ALL INFORMATION AS |
| REQUIRED. |
| PLEASE SEE FS 481.221, WHICH REQUIRES |
| SIAGNTURE. |
| |
| 6)NOTE: PLEASE SEE FAC 61G1-16.004, |
| AND FS 481.219. |
| PLEASE INCLUDE ALL LICENSE #'S ON TITLE |
| BLOCK AS REQUIRED PER ABOVE. |
| |
| 7)NOTE: PLEASE INCLUDE GROUNDING ELEC- |
| -TRODE SYSTEM. 250.50. NO DETAIL GIVEN. |
| |
| 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON |
| PLANS AND DISC'S PER 440.11 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| AS THEY MAY AFFECT ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |