2004-06-30 00:00:00PROVISO:
 RETURN AIR REQUIRED FROM ALL ROOMS THAT
 ARE SEPARATED BY A DOOR FROM THE RETURN
 AIR PLENUM.SEE THE ATTACHED SCHEDULE
 FOR PROPER SIZING.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.