Plan Review Notes For Permit 04061155 |
Permit Number |
04061155 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-29 00:00:00 | PROVISO: | | RETURN AIR REQUIRED FROM THE 2ND FLOOR | | LIBRARY AREA.RETURN AIR ALSO REQUIRED | | FROM ALL ROOMS ON THE 1ST FLOOR THAT ARE | | SEPARATED BY A DOOR FROM THE RETURN AIR | | PLENUM. REVISED 2001 FBC(M) 601.4. | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | DUCTWORK UNDER THE HOUSE SHALL NOT BE | | IN OR WITHIN 6" OF THE GROUND. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|