Date |
Text |
2004-07-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHTS A-1 & A-3, FLOOR PLAN SHOWS THE |
| CLEAR FLOOR SPACE FOR THE LAV IN TOILET |
| ROOM AS FRONTAL APPROACH GOING UNDER THE |
| LAV. DETAILS #14 & #16 SHOW A VANITY |
| CABINET. PLEASE CLAIRFY. SECTION 104.2.1 |
| 2) SHOW THE FOLLOWING INFORMATION FOR |
| THE FOLLOWING ACCESSIBLE FIXTURES ON THE |
| DETAILS. 11-4.16.2 CLEAR FLOOR SPACE, |
| 11-4.16.3 HEIGHT, 11-4.16.5 FLUSH CONTR- |
| OLS, - 11-4.19.2 HEIGHT AND CLEARANCES. |
| 11-4.19.3 CLEAR FLOOR SPACE, 11-4.19.4 |
| EXPOSED PIPES AND SURFACES, - 11-4.24.3 |
| KNEE CLEARANCES, 11-4.24.4 DEPTH, 11-4. |
| 24.5 CLEAR FLOOR SPACE, 11-4.24.6 EX- |
| POSED PIPES AND SURFACES. |
| 3) SHOW TURNING AREA IN TOILET ROOM 110 |
| AND LOUNGE ROOM 108. SECTIONS 11-4.22.3 |
| AND 11-4-2-3. |
| 4) PER TABLE 403.1 A DRINKING FOUNTAIN |
| IS REQUIRED. ALSO SEE SECTION 410.1 |
| 5) WATER CLOSET SHALL BE 18" OFF WALL |
| PER FIG. 28. LAV SHALL BE MIN. 15" OFF |
| WALL TO BE CENTERED ON 30" CLEAR FLOOR |
| SPACE. PLEASE INDICATE ON PLANS. SECTION |
| 104.2.1. |
| 6) SHT P5.1 WATER ISOMETRIC, WATER HAMM- |
| ER ARRESTORS SHALL BE LOCATED NEAR THE |
| FIXTURES IN AN "EFFECTIVE RANGE" NOT IN |
| THE CEILING AS SHOWN. PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. |
| |
| REVIEW BY KEN STEVENS |