2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A-1 & A-3, FLOOR PLAN SHOWS THE
 CLEAR FLOOR SPACE FOR THE LAV IN TOILET
 ROOM AS FRONTAL APPROACH GOING UNDER THE
 LAV. DETAILS #14 & #16 SHOW A VANITY
 CABINET. PLEASE CLAIRFY. SECTION 104.2.1
 2) SHOW THE FOLLOWING INFORMATION FOR
 THE FOLLOWING ACCESSIBLE FIXTURES ON THE
 DETAILS. 11-4.16.2 CLEAR FLOOR SPACE,
 11-4.16.3 HEIGHT, 11-4.16.5 FLUSH CONTR-
 OLS, - 11-4.19.2 HEIGHT AND CLEARANCES.
 11-4.19.3 CLEAR FLOOR SPACE, 11-4.19.4
 EXPOSED PIPES AND SURFACES, - 11-4.24.3
 KNEE CLEARANCES, 11-4.24.4 DEPTH, 11-4.
 24.5 CLEAR FLOOR SPACE, 11-4.24.6 EX-
 POSED PIPES AND SURFACES.
 3) SHOW TURNING AREA IN TOILET ROOM 110
 AND LOUNGE ROOM 108. SECTIONS 11-4.22.3
 AND 11-4-2-3.
 4) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1
 5) WATER CLOSET SHALL BE 18" OFF WALL
 PER FIG. 28. LAV SHALL BE MIN. 15" OFF
 WALL TO BE CENTERED ON 30" CLEAR FLOOR
 SPACE. PLEASE INDICATE ON PLANS. SECTION
 104.2.1.
 6) SHT P5.1 WATER ISOMETRIC, WATER HAMM-
 ER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  