Plan Review Notes
Plan Review Notes For Permit 04061070
Permit Number 04061070
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-15 00:00:00************** UNSAT **************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 HAVE NOT YET BEEN ADDRESSED.
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE LIST/SHOW/INDICATE SIGN
 CIRCUIT AS REQUIRED PER 600.5
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SUBMIT LOAD CALCS FOR EXISTING
 SERVICE. PLEASE SEE WHAT WAS SUBMITTED
 FOR REFERENCE TO PREVIOUS PERMITS DOES
 NOT INDICATE LOAD CALCS.
  
 4)NOTE; PLEASE SEE RISER, STILL DOES NOT
 INDICATE ANY CONDUIT TO NEW SUB-PANELS,
 FEEDERS, EQUIPMENT GRNDS ETC.
 215.5,310.16,250.24,250.110,250.122 ETC
  
 5)NOTE: PLEASE SEE LETTER FROM FPL FOR
 AVAILABLE FAULT CURRENT IS NOW ATTACHED
 BUT THERE IS NO INDICATION FOR RATING
 OF MAINS. 110.9
  
 6)NOTE: PLEASE SEE SUB PANELS ARE NOTED
 ON PLANS AS BEING 125A AND 150A?
 PLEASE VERIFY AND CORRELATE.
  
 7)NOTE: PLEASE SEE TITLE BLOCK IS REQ'D
 TO HAVE THE PRINTED LICENSE # OF
 ENGINEER. FAC 61G15-23.002. FS 471.025
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B) WITH RESPECT TO DESIGN PROFESSIONAL,
 THIS IS GIVEN AS A NOTICE FOR PLANS
 FAILED FOR THE SECOND REVIEW WHICH HAVE
 ONE OR MORE OF THE SAME CODE COMMETS.
 THIS IS A NOTICE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  