Date |
Text |
2004-07-15 00:00:00 | ************** UNSAT ************** |
| |
| PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| HAVE NOT YET BEEN ADDRESSED. |
| |
| 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| AND CORRELATE WITH THE SUBMITTED PANEL |
| SCHEDULE. |
| |
| 2)NOTE: PLEASE LIST/SHOW/INDICATE SIGN |
| CIRCUIT AS REQUIRED PER 600.5 |
| |
| 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| PLEASE SUBMIT LOAD CALCS FOR EXISTING |
| SERVICE. PLEASE SEE WHAT WAS SUBMITTED |
| FOR REFERENCE TO PREVIOUS PERMITS DOES |
| NOT INDICATE LOAD CALCS. |
| |
| 4)NOTE; PLEASE SEE RISER, STILL DOES NOT |
| INDICATE ANY CONDUIT TO NEW SUB-PANELS, |
| FEEDERS, EQUIPMENT GRNDS ETC. |
| 215.5,310.16,250.24,250.110,250.122 ETC |
| |
| 5)NOTE: PLEASE SEE LETTER FROM FPL FOR |
| AVAILABLE FAULT CURRENT IS NOW ATTACHED |
| BUT THERE IS NO INDICATION FOR RATING |
| OF MAINS. 110.9 |
| |
| 6)NOTE: PLEASE SEE SUB PANELS ARE NOTED |
| ON PLANS AS BEING 125A AND 150A? |
| PLEASE VERIFY AND CORRELATE. |
| |
| 7)NOTE: PLEASE SEE TITLE BLOCK IS REQ'D |
| TO HAVE THE PRINTED LICENSE # OF |
| ENGINEER. FAC 61G15-23.002. FS 471.025 |
| |
| PLEASE SEE ATTACHED COPY OF FS 553.80(2) |
| (B) WITH RESPECT TO DESIGN PROFESSIONAL, |
| THIS IS GIVEN AS A NOTICE FOR PLANS |
| FAILED FOR THE SECOND REVIEW WHICH HAVE |
| ONE OR MORE OF THE SAME CODE COMMETS. |
| THIS IS A NOTICE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |