2004-07-06 00:00:00DENIED:
 PERMIT APPLICATION INDICATES INTERIOR
 PARTITION & 2 ELEC SUB-PANELS.PLEASE
 CLARIFY.IS THIS AN INTERIOR BUILD
 OUT?IS THIS SPACEOCCUPIED?
  
 1. INDICATE EQUIPMENT SCHEDULE. NEW OR
 EXISTING.
  
 2. PROVIDE DUCT & GRILLE SIZE, MATERIAL,
 AND LAYOUT FOR ALL NEW DUCTWORK.
 INDICATE EXISTING DUCTWORK.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  