Plan Review Notes
Plan Review Notes For Permit 04061070
Permit Number 04061070
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-06-24 00:00:001) PLANS DISPLAY A PROPOSED STORAGE
 AREA UNDERNEATH EXIT STAIRS WITH NO
 FIRE RATING. PLEASE REVIEW NFPA 101,
 THE LIFE SAFETY CODE, SECTION 7.2.2.5.3,
 2000 EDITION.
  
 2) NO EMERGENCY LIGHTING SHOWN IN
 ONE OF THE SECOND FLOOR TENANT
 SPACES.
  
 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR NEW ALUMINUM RAILING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910