2004-06-22 00:00:00 | ************ UNSAT **************** |
| |
| 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING |
| ON PLANS AND CORRELATE W/ PANEL SCHEDULE |
| -S TO BE SUBMITTED. |
| PLEASE ALSO SEE 700.12E FOR EM/EXT LTS. |
| PLEASE PROVIDE ALL CIRCUITING TO |
| SEPARATE TENANT SPACES. |
| |
| 2)NOTE: PLEASE SEE PLANS AND PERMIT |
| APPLICATION INDICATE TWO NEW SUB PANELS |
| BEING INSTALLED , YET NO INFORMATION IS |
| PROVIDED ON A RISER DIAGRAM ETC? |
| ADDTIONAL SERVICES ARE NOT PERMITTED, |
| MUST COME FROM EXSITING SERVICE. |
| MAY HAVE ADDTIONAL METERS. |
| |
| 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| PLEASE PROVIDE LOAD CALCS FOR EXSITING |
| SERVICE. |
| |
| 4)NOTE: PLEASE INDICATE REQUIRED CIRCUIT |
| PER 600.5 |
| |
| 5)NOTE: PLEASE PROVIDE USEAGE AND OR |
| NEW/ EXSITING SHOW WINDOW RECEPTS REQ'D |
| PER 210.62. |
| |
| 6)NOTE: PLEASE VERIFY A/C SYSTEMS AND |
| WHICH SYSTEM IS FEEDING WHICH AREA. |
| PLANS ONLY SHOW ONE AHU? |
| PLEASE SHOW ALL, AND DISC'S PER 440.11 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |