Plan Review Notes
Plan Review Notes For Permit 04061070
Permit Number 04061070
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-22 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING
 ON PLANS AND CORRELATE W/ PANEL SCHEDULE
 -S TO BE SUBMITTED.
 PLEASE ALSO SEE 700.12E FOR EM/EXT LTS.
 PLEASE PROVIDE ALL CIRCUITING TO
 SEPARATE TENANT SPACES.
  
 2)NOTE: PLEASE SEE PLANS AND PERMIT
 APPLICATION INDICATE TWO NEW SUB PANELS
 BEING INSTALLED , YET NO INFORMATION IS
 PROVIDED ON A RISER DIAGRAM ETC?
 ADDTIONAL SERVICES ARE NOT PERMITTED,
 MUST COME FROM EXSITING SERVICE.
 MAY HAVE ADDTIONAL METERS.
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE PROVIDE LOAD CALCS FOR EXSITING
 SERVICE.
  
 4)NOTE: PLEASE INDICATE REQUIRED CIRCUIT
 PER 600.5
  
 5)NOTE: PLEASE PROVIDE USEAGE AND OR
 NEW/ EXSITING SHOW WINDOW RECEPTS REQ'D
 PER 210.62.
  
 6)NOTE: PLEASE VERIFY A/C SYSTEMS AND
 WHICH SYSTEM IS FEEDING WHICH AREA.
 PLANS ONLY SHOW ONE AHU?
 PLEASE SHOW ALL, AND DISC'S PER 440.11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW