1 |
|
Notes |
Date |
Text |
2004-07-07 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | FBC-2001 CHAPTER 1 | | | | 1) SPA LAYOUT SHALL REFLECT THE DRAIN | | DETAIL. DRAIN DETAIL SHOWS PIPING FOR | | MAIN DRAINS AND SPA DEAINS CONNECTING AT | | THE CENTER OF THE DRAINS, BUT THE SPA | | LAYOUT SHOWS THE PIPING OFFSET FROM THE | | CENTER OF THE DRAINS. THESE SUCTION IN- | | LETS SHALL BE PLUMBED SUCH THAT WATER IS | | DRAWN THROUGH THEM SIMULTANEOUSLY. SEC. | | 424.2.6.6.4. PLEASE CORRELATE DETAIL | | WITH SPA LAYOUT. SECTION 104.2.1. | | 2) WHITE OUT AND HAND WRITTEN DETAILS OR | | NOTES ARE NOT APPROVED ON SIGNED & SEAL- | | ED PLANS. SECTION 104.2.1.3. | | 3) PLEASE CHANGE NOTE #2 TO READ ANSI- | | NSPI-5 (STANDARD FOR RESIDENTIAL SWIMM- | | ING POOLS). HAS BEEN ANSI-NSPI 4. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|