Plan Review Notes
Plan Review Notes For Permit 04061029
Permit Number 04061029
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) POOL LAYOUT SHALL REFLECT THE DRAIN
 DETAIL. DRAIN DETAIL SHOWS PIPING FOR
 MAIN DRAINS AND SPA DRAIN CONNECTING AT
 THE CENTER OF THE DRAINS, BUT POOL LAY-
 OUT SHOWS THE PIPING OFFSET FROM CENTER
 OF DRAINS. THESE SUCTION INLETS SHALL BE
 PLUMBED SUCH THAT WATER IS DRAWN THROUGH
 THEM SIMULTANEOUSLY. SECTION 424.2.6.6.4
 PLEASE CORRELATE DETAIL WITH POOL LAYOUT
 SECTION 104.2.1.
 2) WHITE OUT AND HAND WRITTEN DETAILS OR
 NOTES ARE NOT APPROVED ON SIGNED & SEAL-
 ED PLANS. SECTION 104.2.1.3.
 3) PLEASE CHANGE NOTE #2 TO READ ANSI-
 NSPI-5 (STANDARD FOR RESIDENTIAL SWIMM-
 ING POOLS). HAS BEEN ANSI-NSPI 4
  
 REVIEW BY KEN STEVENS