Date |
Text |
2006-09-08 00:00:00 | **** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE THAT ELECTRICAL |
| SERVICE SIZE HAS NOW BEEN INCREASED TO |
| 325A'S, PLEASE SHOW AND INDICATE THE |
| SIZE OF THE METER CAN ON RISER. |
| PLEASE ALSO CLARIFY THE SEC'S, IF THESE |
| ARE BY FPL, PLEASE DO NOT INCLUDE ON |
| RISER AND NOTE BY FPL. IF THESE ARE |
| BEING INSTALLED BY THE EELECTRICAL |
| CONTRACTOR TO AN FPL HAND HOLE, THEN |
| SIZE SHALL BE DONE IN ACCORDNACE WITH |
| NEC. 310.15B6. |
| PREVIOUS SIZE WAS 3/0'S AND NOW GOING |
| DOWN TO 2/0'S. |
| PLEASE SEE LOADS SHOWN. |
| |
| 2) NOTE: PLEASE SEE NOW THE GROUNDIGN |
| ELECTRODE CONDUCTOR IS BEING DOWN SIZED |
| TO #4, WHEN 250.66 REQUIRES A #2 MIN. |
| PLEASE SEE THAT ALL PREVIOUS PLANS |
| SHOWED A #2 AND A #2 WILL BE REQUIRED. |
| 310.15B6, 250.66 |
| |
| 3) NOTE: PLEASE SEE PREVIOUS PLANS WHICH |
| WERE REDLINED FOR MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN HOUSE TO |
| DETACHED BLDG. THIS IS STILL MISSING AND |
| NOT BEING SHOWN. |
| PLEASE SEE 250.122 AS THE SIZE OF THE |
| FEED FROM THE MAIN IS NOW CHANGED,. |
| PLEASE ALSO SEE MISSIGN GROUNDING |
| ELECTRODE CONDUCTOR SIZE IS MISSIGN AT |
| THE DETACHED BLDG. THIS WAS REDLINED ON |
| ALL PREVIOUS PLANS, HOWEVER ALSO IS |
| STILL NOT SHOWN. PLEASE SEE 250.66 FOR |
| MIN SIZE REQUIRED. |
| |
| 4) NOTE: PLEASE CORRLELATE ALL PLANS, |
| RISER AND PANEL SCHEDULES AS PANEL "A" |
| IS NOW BEING SHOWN AS 125A'S ONRISER. |
| PLEASE SEE PLANS AND PANEL SCHEDULE DOES |
| NOT SHOW THE SAME. |
| 215.5,408.4, 230.90 ETC |
| FBC 106.1.2 |
| PLEASE SEE PLANS ALSO STILL INDICATE A |
| METER/MAIN COMBO? |
| |
| ** PLEASE CORRELATE ALL EQUIPMENT ON |
| SITE WITH PLANS AND BE SURE ALL IS CODE |
| COMPLIANT. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |