2006-06-12 00:00:00********* UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS INDICATE TWO
 MAIN DISC'S AND A MCB PANEL "B".
 PLEASE SEE RISER DOES NOT CORRELATE WITH
 THIS.
 IF PANEL "B' IS LOCATED OUTSIDE AT
 METER, THEN AN ADDTIONAL MAIN DISCONNECT
 IS NOT REQUIRED, HOWEVER MAY BE
 INSTALLED.
 PLEASE SEE THE MAIN ON PLANS FOR PANEL
 "A" IS MISSING FROM RISER.
 PLEASE CORRELATE AND GROUP PER 230.72.
  
 2) NOTE: PLEASE SEE NOW THAT THE
 GROUNDING ELECTRODE SYSTEM IS REVISED, A
 #6 IS NOW BEING SHOWN TO FOOTER STEEL
 WHICH IS WAY TOO SMALL AND DOES NOT MEET
 250.66. PLEASE SEE MIN SIZE REQUIRED IS
 A #2 AS SHOWN ON THE REST OF THE
 GROUNDING ELECTRODE SYSTEM.
  
  
 3) NOTE: PLEASE SEE A SD IS REQUIRED AT
 FIRST FLR LEVEL IN THE IMMEDIATE
 VICINITY OF THE FLR LEADING TO THE FLR
 ABOVE. NFPA-72 8-1.4.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  