2006-05-16 00:00:00 | *********** UNSAT ********* |
| |
| ** PLEASE SEE NOW PLANS ARE COMING IN |
| REVISING RISER ETC FROM ORIGINAL AND |
| PREVIOUS PLANS. PLEASE SEE NOTES BELOW. |
| |
| 1) NOTE: PLEASE SEE MAINS ARE NOW NO |
| LONGER GROUPED PER 230.72 |
| PLEASE SEE PANEL "A" IS SHOWN AS A MCB |
| LOCATED AT GARAGE??? |
| PLEASE SEE ORIG PLANS SHOWED THE SERVICE |
| AT THE GARAGE AND THE PANEL "B" WAS AT |
| HOUSE?? |
| |
| 2) NOTE: PLEASE SEE CIRCUITS FEEDING |
| GARAGE ARE NOW BEING SHOWN COMING FROM |
| THE MAIN HOUSE PANEL? |
| THIS IS NOT PERMIITED AS THE GARAGE |
| CIRCUITS MUST COME FROM THE GARAGE |
| PANEL. |
| PLEASE ALSO SEE PANEL SCHEDULE FOR GAR, |
| DOES NOT SEEM TO INDICATE THE ACURATE |
| CIRCUITS NEED. (LT, GDO ETC). |
| 215.5, 225.31-225.39 ETC. |
| |
| 3) NOTE: PLEASE SEE PANEL SCHEDULES |
| SHALL BE ACCURATE. PANEL SCHEDULES MAY |
| NOT JUST MENTION "GEN LTS AND RECEPTS". |
| IE: MASTER BEDRM LTS, KTICHEN LTS, NW |
| BEDRM RECEPTS ,,,, ETC. |
| 408.4, 215.5 |
| |
| 4) NOTE: PLEASE KNOW, IF PANEL "A" IS |
| NOW AT THE GARAGE AND THE SERVICE IS AT |
| THE MAIN HOUSE, PLEASE RELOCATE THE |
| GROUNDING ELECTRODE SYSTEM FOR THE |
| GARAGE BLDG PER 250.32. THIS SHOWN FOR |
| PANEL "B"?, HOWEVER SHOULD BE SHOWN ON |
| PANEL "A", AS PANEL "B" IS NOW LOCATED |
| ON THE SAME STRUCTURE AS SERVICE. |
| |
| 5) NOTE: PLEASE LABEL ALL SWITCHES |
| ACCORDINGLY. IF A 3-WAY, SW, LABEL. |
| |
| 6) NOTE: PLEASE SEE SD FOR FOYER SEEMS |
| TO MISSING OR RATHER NOT LOCATED IN THE |
| CORRECT VICINITY AS SHOWN ON PLANS. |
| PLEASE SEE NFPA-72, 8-1.4.6.2 WHICH |
| REQUIRES THE SD IN THE IMMEDIATE |
| VICINITY LEADING TO THE FLOOR ABOVE. ( |
| FOYER, MAY REQUIRE SD TO BE WALL MOUNTED |
| ID NO CEILING IS PRESENT. SD AS SHOWN ON |
| PLANS, IS SHOWN IN ANOTHER ROOM. |
| |
| PLEASE SUBMIT TEH ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |