2004-08-04 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) NEW PLANS NEED TO BE RESTAMPED BY |
| THE CITY HISTORIC PRESERVATION DEPT. |
| |
| 3)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| SUBMIT THE FLORIDA PRODUCT IDENTITY |
| NUMBER FOR WINDOWS, DOORS, ROOFING, AND |
| OTHER STRUCTURAL ITEMS LISTED IN RULE |
| 9B-72. |
| |
| 4)THE PLANS SPECIFY ALL EXTERIOR GLAZING |
| TO BE IMPACT RESISTANT. THE PRODUCT |
| INFORMATION THAT WAS SUBMITTED IS FOR |
| NON IMPACT RATED. PLEASE CORRECT. |
| |
| 5) SUBMIT A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS IN |
| ADDITION TO THE STATE PRODUCT APPROVAL, |
| IF GLAZING IS NOT IMPACT RESISTANT. |
| |
| 6) SUBMIT STATE PRODUCT APPROVALS FOR |
| THE FOLLOWING: |
| - GLAZED DOUBLE AND SINGLE FRENCH DOORS |
| (IMPACT RATED) |
| - GLAZED DOUBLE OUTSWING DOORS WITH |
| SIDELITES (IMPACT RATED) |
| - SINGLE OUTSWING FIBERGLASS OR STEEL |
| DOOR AT GARAGE (IMPACT RATED) |
| - CASEMENT WINDOWS (IMPACT RATED) |
| - STRUCTURAL MULLIONS (IMPACT RATED) |
| - SINGLE OUTSWING ENTRY DOOR "PEC. WOOD" |
| (IMPACT RATED) |
| |
| 7) THE ENERGY CALCULATION FORMS SPECIFY |
| A CEILING FAN CREDIT. THE PLANS DO NOT |
| INDICATE ANY CEILING FANS IN THE FAMILY |
| ROOM. THE FBC CHAPTER 13-607.1A.1 |
| REQUIRES 2 FANS (MINIMUM OF 48" EACH) IN |
| THIS ROOM. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |