Plan Review Notes
Plan Review Notes For Permit 04060959
Permit Number 04060959
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-01 00:00:00DENIED;
 1.NOTE 6. SHOULD READ, SHOCK ARRESTORS
 TO BE INSTALLED PER SEC. 604.9.
 2.RISER DIAGRAM AND FLOOR PLAN FLAT LINE
 DRAWING NOT TO CODE.
 A.2ND FL TUB BATH, TUB IS NOT VENTED
 B.L/T NOT SHOWN ON RISER DIAGRAM.
 C.1ST FLOOR MASTER BATH W/M MUST TIE
 IN DOWN STREAM OF THE BATHROOM
 GROUP. SEE SEC. 909.1.
 D.SIZE ALL PIPE ON FLAT DRAWING OR
 RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;