Plan Review Notes For Permit 04060959
Permit Number 04060959
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-29 00:00:00DENIED:
 1.RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PER THE REVISED 2001 FBC(M)
 601.4 EXCEPTION #1, RETURN AIR TRANSFER
 DUCTS ARE TO BE SIZED 1 1/2 TIMES THE
 SUPPLY AIR TO THAT AREA.THE MASTER
 SUITE IS TO INCLUDE ALL SUUPLY AIR TO
 THE SUITE (BATHROOMS, CLOSET, DRESSING
 ROOM, ETC).PLEASE SEE THE ATTACHED
 SCHEDULE FOR PROPER SIZING OF THE RETURN
 AIR JUMPERS.
  
 2.PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13
 SUB-CHAPTER 6.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED, 2001 FBC(M) 307.2.3
  
 IF YOU HAVE ANY QUESTIONS, PLEASE