Plan Review Notes For Permit 04060959 |
Permit Number |
04060959 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-06-29 00:00:00 | DENIED: | | 1.RETURN AIR JUMPERS ARE NOT SIZED | | PROPERLY.PER THE REVISED 2001 FBC(M) | | 601.4 EXCEPTION #1, RETURN AIR TRANSFER | | DUCTS ARE TO BE SIZED 1 1/2 TIMES THE | | SUPPLY AIR TO THAT AREA.THE MASTER | | SUITE IS TO INCLUDE ALL SUUPLY AIR TO | | THE SUITE (BATHROOMS, CLOSET, DRESSING | | ROOM, ETC).PLEASE SEE THE ATTACHED | | SCHEDULE FOR PROPER SIZING OF THE RETURN | | AIR JUMPERS. | | | | 2.PLEASE PROVIDE ENERGY AND MANUAL J | | CALCULATIONS PER 2001 FBC CHAPTER 13 | | SUB-CHAPTER 6. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED, 2001 FBC(M) 307.2.3 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|