2004-07-08 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT TWO COPIES OF A RECENT SURVEY. |
| |
| 4) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 5) PLANS DO NOT CLEARLY INDICATE THE |
| PROTION OF THE STRUCTURE THAT IS EXIST- |
| ING. PLEASE CLARIFY. |
| |
| 6) THE FIRM LICENSE NUMBER IS NOT GIVEN |
| IN THE TITLE BLOCK. SEE FAC 61G1-16.004. |
| |
| 7) A SEPARATE PERMIT IS REQUIRED FOR THE |
| SITE WALLS. |
| |
| 8) THE FULL BATH ON THE FIRST FLOOR IS |
| REQUIRED TO HAVE DOORS WITH 29" CLEAR |
| OPENING PER FBC 11-4.22.2. |
| |
| 9) FBC MECHANICAL CODE 304.6 REQUIRES |
| HEAT PRODUCING APPLIANCES TO MAINTAIN |
| CLEARANCES TO COMBUSTABLE CONSTRUCTION, |
| INCLUDING SHUTTERS AND DRAPES. LOCATION |
| OF WINDOW ABOVE COOKTOP IN KITCHEN. |
| |
| 10) AT LEAST ONE WINDOW IN SECOND FLOOR |
| BEDROOMS MUST COMPLY WITH EGRESS. SEE |
| FBC 1005.4. THE (F) WINDOWS IN THE |
| SCHEDULE ON SHEET 2 SHOULD BE MARKED |
| EGRESS. |
| |
| 11) SPECIFY FIREBLOCKING AT CONCEALED |
| SPACES BETWEEN STAIR STRINGERS AT THE |
| TOP AND BOTTOM OF RUNS AS REQUIRED BY |
| FBC 2305.1.4. |
| |
| 12) SPECIFY THE REQUIRED CLEARANCES OF |
| EXISTING CHIMNEY FROM ROOF AND NEW |
| CONSTRUCTION. SEE FBC 2804.2.4. |
| |
| 13) SHOW COMPLIANCE WITH FBC 1503.4.4 |
| WHICH REQUIRES DOWNSPOUTS TO DISCHARGE |
| AT LEAST 12" FROM SIDEWALLS OF THE |
| STRUCTURE AND GUTTERS WITH DOWNSPOUTS ON |
| BUILDINGS WITH EAVES OF LESS THAN 6" |
| PROJECTIONS. |
| |
| 14) THE POSITIVE AND NEGATIVE SIGNS ARE |
| MISSING FROM THE INTERNAL PRESSURE |
| COEFFICENT ON SHEET 5. |
| |
| 15)TWO DIFFERENT SOIL BEARING CAPACITIES |
| ARE GIVEN ON SHEET 5. PLEASE CORRECT. |
| |
| 16) TWO DIFFERENT STRENGTHS OF CONCRETE |
| ARE SPECIFIED ON SHEET5. THE FOOTING |
| SCHEDULE HAS 2500 PSI AND THE FOUNDATION |
| PLAN LISTS 3000 PSI CONCRETE. PLEASE |
| CORRECT. |
| |
| 17) SPECIFY HOW THE SECTION OF THE |
| SECOND FLOOR BLOCK WALL AND CONC. COLUMN |
| ABOVE THE EXISTING MASTER BEDROOM WILL |
| BE SUPPORTED FROM BELOW. |
| |
| 18) REVISE THE DIAGRAM OF THE HIP ROOF |
| NAILING ZONES ON SHEET 7. THE OUTSIDE |
| CORNERS OF HIP ROOFS ARE ALSO ZONE 3. |
| SEE CITY OF WPB AMENDMENTS TO FBC TABLE |
| 2306.1. |
| |
| 19)SPECIFY FIREBLOCKING ON WALL SECTIONS |
| FBC 2305.1.4 REQUIRES CONCEALED SPACES |
| OF STUD WALLS AND PARTITIONS INCLUDING |
| FURRED SPACES TO BE FIREBLOCKED AT |
| CEILING AND FLOOR LEVELS AND WHERE WALLS |
| AND FLOORS OR TRUSSES MEET. |
| |
| 20) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| SUBMIT PRODUCT APPROVALS FOR EXTERIOR |
| WINDOWS, DOORS, MULLIONS, OVERHEAD |
| GARAGE DOORS, ETC. |
| |
| 21) SUBMIT A KEY PLAN, INSTALLATION |
| SCHEDULE AND PRODUCT APPROVAL FOR STORM |
| PANELS (UNLESS IMPACT GLAZING IS USED). |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |