2004-07-08 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF A RECENT SURVEY.
  
 4) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 5) PLANS DO NOT CLEARLY INDICATE THE
 PROTION OF THE STRUCTURE THAT IS EXIST-
 ING. PLEASE CLARIFY.
  
 6) THE FIRM LICENSE NUMBER IS NOT GIVEN
 IN THE TITLE BLOCK. SEE FAC 61G1-16.004.
  
 7) A SEPARATE PERMIT IS REQUIRED FOR THE
 SITE WALLS.
  
 8) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE DOORS WITH 29" CLEAR
 OPENING PER FBC 11-4.22.2.
  
 9) FBC MECHANICAL CODE 304.6 REQUIRES
 HEAT PRODUCING APPLIANCES TO MAINTAIN
 CLEARANCES TO COMBUSTABLE CONSTRUCTION,
 INCLUDING SHUTTERS AND DRAPES. LOCATION
 OF WINDOW ABOVE COOKTOP IN KITCHEN.
  
 10) AT LEAST ONE WINDOW IN SECOND FLOOR
 BEDROOMS MUST COMPLY WITH EGRESS. SEE
 FBC 1005.4. THE (F) WINDOWS IN THE
 SCHEDULE ON SHEET 2 SHOULD BE MARKED
 EGRESS.
  
 11) SPECIFY FIREBLOCKING AT CONCEALED
 SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF RUNS AS REQUIRED BY
 FBC 2305.1.4.
  
 12) SPECIFY THE REQUIRED CLEARANCES OF
 EXISTING CHIMNEY FROM ROOF AND NEW
 CONSTRUCTION. SEE FBC 2804.2.4.
  
 13) SHOW COMPLIANCE WITH FBC 1503.4.4
 WHICH REQUIRES DOWNSPOUTS TO DISCHARGE
 AT LEAST 12" FROM SIDEWALLS OF THE
 STRUCTURE AND GUTTERS WITH DOWNSPOUTS ON
 BUILDINGS WITH EAVES OF LESS THAN 6"
 PROJECTIONS.
  
 14) THE POSITIVE AND NEGATIVE SIGNS ARE
 MISSING FROM THE INTERNAL PRESSURE
 COEFFICENT ON SHEET 5.
  
 15)TWO DIFFERENT SOIL BEARING CAPACITIES
 ARE GIVEN ON SHEET 5. PLEASE CORRECT.
  
 16) TWO DIFFERENT STRENGTHS OF CONCRETE
 ARE SPECIFIED ON SHEET5. THE FOOTING
 SCHEDULE HAS 2500 PSI AND THE FOUNDATION
 PLAN LISTS 3000 PSI CONCRETE. PLEASE
 CORRECT.
  
 17) SPECIFY HOW THE SECTION OF THE
 SECOND FLOOR BLOCK WALL AND CONC. COLUMN
 ABOVE THE EXISTING MASTER BEDROOM WILL
 BE SUPPORTED FROM BELOW.
  
 18) REVISE THE DIAGRAM OF THE HIP ROOF
 NAILING ZONES ON SHEET 7. THE OUTSIDE
 CORNERS OF HIP ROOFS ARE ALSO ZONE 3.
 SEE CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1.
  
 19)SPECIFY FIREBLOCKING ON WALL SECTIONS
 FBC 2305.1.4 REQUIRES CONCEALED SPACES
 OF STUD WALLS AND PARTITIONS INCLUDING
 FURRED SPACES TO BE FIREBLOCKED AT
 CEILING AND FLOOR LEVELS AND WHERE WALLS
 AND FLOORS OR TRUSSES MEET.
  
 20) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 WINDOWS, DOORS, MULLIONS, OVERHEAD
 GARAGE DOORS, ETC.
  
 21) SUBMIT A KEY PLAN, INSTALLATION
 SCHEDULE AND PRODUCT APPROVAL FOR STORM
 PANELS (UNLESS IMPACT GLAZING IS USED).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714